SUCHEN SIE DIE PASSENDE

INDUSTRIELLE LÖSUNG?

Entdecken Sie Embedded-, Kommunikations- und Automatisierungslösungen für Ihre Anwendung.

PCI-7233H

PCI isolated Digital IO Card, 32DI, high speed
  • Hersteller Adlink Technology Inc.
  • Kategorie: DIO Isolated PCI
  • The ADLINK PCI-7233H is a high-performance isolated digital input card designed for industrial automation, data acquisition, and control applications. As part of ADLINK’s PCI-723X family, it provides 32 optically isolated digital input channels with robust protection and high-speed change-of-state (COS) detection. The card interfaces directly with a standard 32-bit, 5 V PCI bus and offers 2.5 kV to 5 kV RMS optical isolation, ensuring reliable operation in electrically noisy environments.
- 32 Isolated Digital Input Channels: Provides 32 optically isolated DI channels for reliable signal acquisition from external devices.
- High-Speed Change-of-State (COS) Detection: Detects input transitions on all 32 channels, generating interrupts for real-time event monitoring.
- High Throughput: Supports input sampling rates up to 500 kHz, suitable for high-speed digital monitoring.
- Optical Isolation: 2.5 kV to 5 kV RMS isolation between channels and host system, protecting against voltage surges and ground loops.
- Non-Polarity Input Design: Accepts non-polarized 0–24 V DC signals, simplifying wiring and integration.
- Compact PCI Form Factor: Standard PCI card dimensions (158 mm × 107 mm) for easy installation in industrial PCs.
- Connector Type: 37-pin female D-sub connector for secure and standardized I/O interfacing.
- Interrupt Support: Dual interrupt sources for COS detection on lower and upper 16-channel groups.
- Wide Input Voltage Range: Accepts 5–24 V logic high and 0–1.5 V logic low levels.
- Software Compatibility: Fully supported by ADLINK’s DAQPilot, PCIS-DASK, and DAQ-MTLB drivers for Windows and Linux, as well as integration with LabVIEW™ and MATLAB®.
- Industrial-Grade Reliability: Designed for 0°C to 60°C operation, with 5–95% non-condensing humidity tolerance.

Ursprungsland: Taiwan R.O.C.

Zolltarifnummer: 8473 3020 000

1. Product Overview

Product Name: PCI-7233H
Model: PCI-7233H
Series: PCI-723X Series (Isolated Digital I/O Cards)
Article Number: PCI-7233H
Manufacturer: ADLINK Technology Inc.
Product Type: PCI Isolated Digital Input (DI) Card, 32 Channels, High-Speed

The ADLINK PCI-7233H is a high-performance isolated digital input card designed for industrial automation, data acquisition, and control applications. As part of ADLINK’s PCI-723X family, it provides 32 optically isolated digital input channels with robust protection and high-speed change-of-state (COS) detection. The card interfaces directly with a standard 32-bit, 5 V PCI bus and offers 2.5 kV to 5 kV RMS optical isolation, ensuring reliable operation in electrically noisy environments.




2. Key Features

- 32 Isolated Digital Input Channels: Provides 32 optically isolated DI channels for reliable signal acquisition from external devices.
- High-Speed Change-of-State (COS) Detection: Detects input transitions on all 32 channels, generating interrupts for real-time event monitoring.
- High Throughput: Supports input sampling rates up to 500 kHz, suitable for high-speed digital monitoring.
- Optical Isolation: 2.5 kV to 5 kV RMS isolation between channels and host system, protecting against voltage surges and ground loops.
- Non-Polarity Input Design: Accepts non-polarized 0–24 V DC signals, simplifying wiring and integration.
- Compact PCI Form Factor: Standard PCI card dimensions (158 mm × 107 mm) for easy installation in industrial PCs.
- Connector Type: 37-pin female D-sub connector for secure and standardized I/O interfacing.
- Interrupt Support: Dual interrupt sources for COS detection on lower and upper 16-channel groups.
- Wide Input Voltage Range: Accepts 5–24 V logic high and 0–1.5 V logic low levels.
- Software Compatibility: Fully supported by ADLINK’s DAQPilot, PCIS-DASK, and DAQ-MTLB drivers for Windows and Linux, as well as integration with LabVIEW™ and MATLAB®.
- Industrial-Grade Reliability: Designed for 0°C to 60°C operation, with 5–95% non-condensing humidity tolerance.




3. Technical Specifications

Digital Input Section
- Number of Channels: 32 isolated digital inputs
- Input Voltage Range: 0–24 V DC, non-polarity
- Logic Levels:
- Logic “High”: 5–24 V
- Logic “Low”: 0–1.5 V
- Input Resistance: 1.2 kΩ ±5%, 0.5 W
- Isolation Voltage: 5,000 V RMS (channel-to-system)
- Throughput Rate: Up to 500 kHz (high-speed version)
- Interrupt Sources: Dual COS interrupts (channels 0–15 and 16–31)
- Data Transfer Mode: Programmed I/O

General Specifications
- Bus Interface: 32-bit, 5 V PCI bus (PCI Local Bus Specification Rev. 2.1 compliant)
- Connector: 37-pin D-sub female
- Dimensions: 158 mm (L) × 107 mm (H)
- Weight: Approx. 200 g (typical)
- Power Consumption: +5 V @ 300 mA (typical)
- Operating Temperature: 0°C to 60°C
- Storage Temperature: -20°C to 80°C
- Relative Humidity: 5% to 95%, non-condensing
- Isolation Type: Optical isolation between input channels and host system

Mechanical and Electrical
- PCB Type: Full-size PCI card
- Mounting: Standard PCI slot mounting bracket
- Isolation Protection: Optical couplers rated up to 5 kV RMS
- Input Protection: Up to 24 V DC overvoltage protection




4. Functionality

The PCI-7233H functions as a high-speed, isolated digital input interface for industrial control systems. Each of its 32 input channels is optically isolated, allowing the card to safely monitor external digital signals such as sensors, switches, and relays without electrical interference or ground potential differences.

Operation Principle:
- External digital signals (0–24 V DC) are applied to the input terminals.
- Each input passes through an opto-isolator, converting the electrical signal into an optical signal for galvanic isolation.
- The optical signal is then converted back to a logic-level signal readable by the PCI controller.
- The card continuously monitors all channels and can generate interrupts when a change of state (COS) occurs on any input line.

Use Cases and Applications:
- Industrial automation and process control
- Machine status monitoring
- Event counting and digital signal logging
- Safety interlock and alarm systems
- Remote sensing and digital input expansion for PLCs or SCADA systems

Compatibility:
- Compatible with standard PCI slots in industrial PCs.
- Supported by ADLINK’s software drivers for Windows and Linux.
- Integrates with third-party environments such as MATLAB® and LabVIEW™.




5. Components & Accessories

Included Items:
- PCI-7233H card
- User’s manual (digital or printed)
- ADLINK software CD (drivers and utilities)
- Software installation guide

Optional Accessories:
- DIN-37D-01: Terminal board with one 37-pin D-sub connector and DIN-rail mounting.
- ACLD-9137-01: General-purpose terminal board with one 37-pin D-sub male connector.
- ACL-10137-1MM: 37-pin D-sub male-to-male cable, 1 meter length.

Connectors:
- I/O Connector: 37-pin D-sub female (isolated digital input signals)
- Onboard Terminals: Power and ground terminals for external reference connections.




6. Installation & Setup

System Requirements:
- Available 32-bit, 5 V PCI slot
- Host PC running Windows 2000/XP/Vista/7 or Linux kernel with PCIS-DASK/X driver support
- External 5–24 V DC input signals

Installation Steps:
1. Power off the host computer and disconnect all peripherals.
2. Insert the PCI-7233H into an available PCI slot.
3. Secure the card with the mounting screw.
4. Connect external digital input signals to the 37-pin D-sub connector.
5. Power on the system; the operating system will automatically detect the card via Plug and Play.
6. Install ADLINK’s DAQPilot or PCIS-DASK driver package.
7. Verify installation using ADLINK’s DAQMaster utility or DAQBench software.

Configuration:
- No manual jumper or DIP switch settings required (Plug and Play).
- Interrupts and I/O addresses are automatically assigned by the system BIOS.
- COS interrupt functionality can be configured via software API.

Mounting Options:
- Standard PCI bracket mounting inside PC chassis.
- External signal wiring via DIN-rail terminal boards for industrial environments.




7. Performance & Capabilities

Speed and Throughput:
- Input sampling rate up to 500 kHz, enabling high-speed digital monitoring.
- COS detection latency in microsecond range for real-time event response.

Capacity:
- 32 independent input channels, each optically isolated.
- Dual-interrupt architecture allows simultaneous monitoring of two 16-channel groups.

Efficiency:
- Low power consumption (1.5 W typical).
- High isolation minimizes noise coupling and ground loop interference.

Limitations:
- Input-only card (no digital output capability).
- Requires external 5–24 V DC input signals.
- COS detection limited to edge-triggered events (no level-triggered interrupts).

Reliability:
- Industrial-grade components rated for continuous operation in harsh environments.
- Optical isolation ensures long-term stability and protection against transient voltages.




8. Standards & Compliance

Bus Compliance:
- PCI Local Bus Specification Revision 2.1
- 32-bit, 5 V signaling

Form Factor:
- Full-size PCI card (158 mm × 107 mm)

Isolation and Safety Standards:
- Optical isolation: 2.5 kV to 5 kV RMS
- Input protection: 24 V DC maximum

Environmental Compliance:
- Operating temperature: 0°C to 60°C
- Storage temperature: -20°C to 80°C
- Humidity: 5–95%, non-condensing

Regulatory Compliance:
- CE and FCC Class A (industrial environment)
- RoHS compliant

Industry Standards:
- Compatible with PICMG 2.0 R2.1 (CompactPCI reference design)
- Supports ADLINK’s NuDAQ and DAQBench software ecosystems




9. Additional Information

Warranty:
- Standard 2-year limited warranty from ADLINK Technology Inc.
- Covers defects in materials and workmanship under normal use.

Technical Support:
- Global support via ADLINK’s service network.
- Contact: service@adlinktech.com
- Website: [www.adlinktech.com](http://www.adlinktech.com)
- Telephone: +886-2-82265877 (Taipei Headquarters)

Maintenance:
- Periodic inspection of connectors and cabling recommended.
- Avoid exposure to excessive humidity or dust.
- Clean with anti-static tools only.

Software & Driver Updates:
- Latest drivers available from ADLINK’s website.
- Supported software packages include:
- DAQPilot: Task-oriented driver and SDK for Windows.
- PCIS-DASK / PCIS-DASK/X: Legacy driver for Windows and Linux.
- DAQ-MTLB: MATLAB® Data Acquisition Toolbox adapter.
- DAQ-LVIEW PnP: LabVIEW™ VI set for ADLINK DAQ cards.
- DAQBench: ActiveX control suite for SCADA/HMI applications.
- DAQMaster: Configuration-based device manager for ADLINK DAQ hardware.

Service and RMA:
- ADLINK provides repair and replacement services through authorized distributors.
- Users should retain original packaging for safe shipment if service is required.

Documentation:
- User’s Manual (Rev. 4.05, Part No. 50-11037-1000)
- Software Installation Guide
- Pin Assignment and Terminal Board Connection Diagrams




### Summary

The ADLINK PCI-7233H is a robust, high-speed, 32-channel isolated digital input card engineered for industrial and laboratory automation systems. It provides reliable signal acquisition with 5 kV optical isolation, high-speed COS detection, and full PCI bus compliance. Its non-polarity input design simplifies wiring, while dual-interrupt COS detection enables responsive event-driven control.

With comprehensive driver support for Windows and Linux, and seamless integration with MATLAB®, LabVIEW™, and SCADA/HMI environments, the PCI-7233H offers a flexible and scalable solution for digital input expansion, monitoring, and control in demanding industrial applications.

Key Advantages:
- 32 isolated DI channels with 5 kV RMS isolation
- High-speed 500 kHz throughput
- COS interrupt detection on all channels
- 37-pin D-sub connector for easy integration
- Full software ecosystem support (DAQPilot, LabVIEW™, MATLAB®)
- Industrial-grade reliability and long-term stability

Ideal Applications:
- Factory automation and process control
- Machine monitoring and safety systems
- Digital signal acquisition and event logging
- SCADA and HMI integration
- Test and measurement systems requiring isolated digital inputs




Manufacturer Contact Information:
ADLINK Technology Inc.
9F, No. 166, Jian Yi Road, Chungho City, Taipei 235, Taiwan
Tel: +886-2-82265877 | Fax: +886-2-82265717
Email: service@adlinktech.com
Website: [www.adlinktech.com](http://www.adlinktech.com)




*All specifications are subject to change without prior notice. ADLINK, NuDAQ, and DAQBench are registered trademarks of ADLINK Technology Inc. Other product names are trademarks of their respective owners.*