  • The ADLINK PCI-9812A is a high-performance, 4-channel, 12-bit, 20 MS/s simultaneous-sampling analog input card designed for industrial, scientific, and engineering data acquisition applications. It is part of ADLINK’s NuDAQ PCI series and represents an enhanced version of the PCI-9812, featuring an expanded 128K-sample FIFO buffer for extended high-speed data capture.
- High-Speed Sampling:
Up to 20 million samples per second (20 MS/s) per channel with true simultaneous sampling across four channels.

- High Resolution:
12-bit resolution A/D conversion using Burr-Brown ADS800 series converters ensures precise signal digitization.

- Simultaneous Sampling Architecture:
Four independent A/D converters allow all channels to sample concurrently, eliminating phase skew between channels.

- Large On-Board FIFO Buffer:
128K-sample A/D FIFO (double the 32K of the PCI-9812) provides extended buffering for high-throughput applications.

- Multiple Input Ranges and Impedances:
Hardware-selectable input ranges of ±1 V and ±5 V, with selectable input impedances of 50 Ω, 1.25 kΩ, or 15 MΩ for flexible signal interfacing.

- Flexible Triggering Options:
Supports software, analog threshold, and external digital triggers with multiple trigger modes: pre-trigger, post-trigger, middle-trigger, delay-trigger, and software-trigger.

- Clock Source Flexibility:
Operates with internal 40 MHz time base, or accepts external digital or sine wave clocks (20 kHz–40 MHz range).

- Bus Mastering DMA:
Direct memory access (DMA) transfers data to host memory without CPU intervention, ensuring efficient high-speed throughput.

- Plug-and-Play PCI Interface:
Fully compliant with 32-bit PCI bus architecture, supporting automatic resource allocation and configuration.

- Comprehensive Software Support:
Includes drivers and libraries for MS-DOS, Windows 95/98/NT, and supports C/C++, LabVIEW, ActiveX (DAQBench), and DASYLab environments.

- Industrial-Grade Design:
Rugged construction with wide operating temperature range and high reliability for continuous operation in demanding environments.

Ursprungsland: Taiwan R.O.C.

Zolltarifnummer: 8473 3020 000

Comprehensive Product Summary: ADLINK PCI-9812A High-Speed Analog Input Card




### 1. Product Overview

Product Name: PCI-9812A
Model: PCI-9812A
Series: PCI-9812/9810/9812A – 4-Channel Simultaneous-Sampling Analog Input Cards
Article Number: PCI-9812A
Manufacturer: ADLINK Technology Inc.
Product Type: PCI Bus Analog-to-Digital (A/D) Data Acquisition Card
Category: PCI DAQ Cards – High-Speed Simultaneous Sampling

The ADLINK PCI-9812A is a high-performance, 4-channel, 12-bit, 20 MS/s simultaneous-sampling analog input card designed for industrial, scientific, and engineering data acquisition applications. It is part of ADLINK’s NuDAQ PCI series and represents an enhanced version of the PCI-9812, featuring an expanded 128K-sample FIFO buffer for extended high-speed data capture. The card integrates advanced A/D conversion technology, flexible triggering, and multiple clocking options, making it suitable for vibration analysis, ultrasonic measurement, image digitization, and other high-speed signal acquisition tasks.




### 2. Key Features

- High-Speed Sampling:
Up to 20 million samples per second (20 MS/s) per channel with true simultaneous sampling across four channels.

- High Resolution:
12-bit resolution A/D conversion using Burr-Brown ADS800 series converters ensures precise signal digitization.

- Simultaneous Sampling Architecture:
Four independent A/D converters allow all channels to sample concurrently, eliminating phase skew between channels.

- Large On-Board FIFO Buffer:
128K-sample A/D FIFO (double the 32K of the PCI-9812) provides extended buffering for high-throughput applications.

- Multiple Input Ranges and Impedances:
Hardware-selectable input ranges of ±1 V and ±5 V, with selectable input impedances of 50 Ω, 1.25 kΩ, or 15 MΩ for flexible signal interfacing.

- Flexible Triggering Options:
Supports software, analog threshold, and external digital triggers with multiple trigger modes: pre-trigger, post-trigger, middle-trigger, delay-trigger, and software-trigger.

- Clock Source Flexibility:
Operates with internal 40 MHz time base, or accepts external digital or sine wave clocks (20 kHz–40 MHz range).

- Bus Mastering DMA:
Direct memory access (DMA) transfers data to host memory without CPU intervention, ensuring efficient high-speed throughput.

- Plug-and-Play PCI Interface:
Fully compliant with 32-bit PCI bus architecture, supporting automatic resource allocation and configuration.

- Comprehensive Software Support:
Includes drivers and libraries for MS-DOS, Windows 95/98/NT, and supports C/C++, LabVIEW, ActiveX (DAQBench), and DASYLab environments.

- Industrial-Grade Design:
Rugged construction with wide operating temperature range and high reliability for continuous operation in demanding environments.




### 3. Technical Specifications

Analog Input:
- Channels: 4 single-ended, simultaneous sampling
- Resolution: 12-bit
- Sampling Rate: Up to 20 MS/s per channel
- Input Ranges: ±1 V, ±5 V (bipolar)
- Input Impedance: 50 Ω, 1.25 kΩ, or 15 MΩ (solder-selectable)
- Accuracy: ±1.5% typical at 25°C
- DNL: ±0.4 LSB typical, ±1.0 LSB max
- INL: ±1.9 LSB typical
- Input Coupling: DC
- Overvoltage Protection: ±10 V (typical)

FIFO Buffer:
- Size: 128K samples (PCI-9812A)
- Data Transfer: Bus mastering DMA

Triggering:
- Sources: Software, analog (CH0–CH3), external digital (TTL)
- Modes: Software, pre-trigger, post-trigger, middle-trigger, delay-trigger
- Analog Trigger Sensitivity: 256 steps across full-scale range
- Digital Trigger Compatibility: 5 V TTL, minimum pulse width 25 ns
- Trigger Slope: Rising/falling edge selectable

Clock Sources:
- Internal Clock: 40 MHz oscillator
- External Digital Clock: 20 kHz–40 MHz, 50 Ω impedance, TTL compatible
- External Sine Wave Clock: 300 kHz–40 MHz, 1.0–2.0 Vpp, 50 Ω impedance
- Clock Divider: Programmable, even values from 2 to 1024

Digital Input:
- Channels: 3 TTL-compatible inputs
- Input Voltage: Low ≤ 0.8 V, High ≥ 2.0 V (max 5.5 V)
- Pull-down Resistors: 10 kΩ
- Overvoltage Protection: Diode clamping, -0.3 V to +5.3 V

Physical Characteristics:
- Dimensions: 173 mm (L) × 108 mm (H)
- Connectors: 5 × BNC (CH0–CH3 + Ext. Sine Clock), 10-pin ribbon header (JP1)
- Weight: Approx. 250 g (typical)
- Power Requirement: +5 V @ 1.4 A typical
- Operating Temperature: 0°C to 40°C
- Storage Temperature: -20°C to 70°C
- Humidity: 5–95% RH, non-condensing




### 4. Functionality

The PCI-9812A functions as a high-speed digitizer for analog signals, converting continuous analog waveforms into digital data streams for processing and analysis. Each of the four channels uses a dedicated 12-bit A/D converter, enabling simultaneous sampling without inter-channel delay. The card’s internal 40 MHz clock or external clock sources control the sampling rate, while the onboard FIFO buffer temporarily stores data before DMA transfer to host memory.

Typical Use Cases:
- Vibration and acoustic analysis
- Ultrasonic and medical imaging
- High-speed signal digitization (IF/baseband)
- Automated test equipment (ATE)
- Scientific instrumentation and research
- CCD and video signal digitizing

Compatibility:
- PCI 2.1 compliant, 32-bit bus
- Supported OS: MS-DOS, Windows 95/98/NT
- Software APIs: C/C++, Visual Basic, LabVIEW, DASYLab, ActiveX




### 5. Components & Accessories

Included Items:
- PCI-9812A analog input card
- 5 × BNC terminators
- ADLINK “All-in-One” software CD (drivers, utilities, libraries)
- User’s Guide and installation documentation

Connectors:
- J1–J4: Analog input channels CH0–CH3 (BNC)
- J5: External sine wave clock input (BNC)
- JP1 (10-pin header):
- Pin 1: External digital clock input
- Pin 3: External digital trigger input
- Pins 5, 7, 9: Digital inputs DI0–DI2
- Even pins: Ground

Optional Accessories:
- Shielded BNC cables
- External clock signal generators
- Termination boards and calibration tools




### 6. Installation & Setup

Hardware Installation:
1. Power off the host PC and remove the cover.
2. Insert the PCI-9812A into an available 32-bit PCI slot.
3. Secure the card and reconnect system power.
4. The system BIOS automatically assigns I/O and IRQ resources (Plug-and-Play).

Software Installation:
- Insert the ADLINK “All-in-One” CD.
- For Windows 95/98: Install drivers from `X:\Win95inf\9812`.
- For DOS: Run `SETUP` from `NuDAQPCI\9812\DOS`.
- Verify installation using the included utility `9812util.exe`.

Configuration:
- Input range and impedance are hardware-selectable via solder jumpers (C0LO/C05V, etc.).
- External clock and trigger connections via BNC and JP1 headers.
- Calibration performed using onboard variable resistors (VR1–VR8).




### 7. Performance & Capabilities

Sampling Performance:
- 4 channels × 20 MS/s × 2 bytes = 160 MB/s total throughput.
- PCI bus peak bandwidth: 132 MB/s; effective sustained rate ~100 MB/s.
- Onboard FIFO (128K samples) buffers data to prevent loss at high rates.

Data Transfer:
- Bus-mastering DMA ensures efficient, CPU-independent data streaming.
- Supports continuous acquisition with double-buffered software techniques.

Limitations:
- When total throughput exceeds PCI bandwidth, acquisition length is limited by FIFO size.
- For 4-channel operation at full rate, maximum continuous samples per channel ≈ 8K.
- For single-channel operation, full 128K-sample FIFO available.

Dynamic Performance:
- Differential Linearity Error (DNL): ±0.4 LSB typical
- Integral Linearity Error (INL): ±1.9 LSB typical
- Gain Error: ±1.5% typical

Data Format:
- 12-bit data stored in 16-bit words (upper 12 bits valid).
- Bipolar representation:
- ±1 V range → ±32752 counts
- ±5 V range → ±32752 counts × 5 scaling




### 8. Standards & Compliance

- Bus Interface: PCI Local Bus Specification Rev. 2.1 compliant
- Electrical Compatibility: TTL-level digital I/O, 5 V logic
- Safety & Environmental:
- Operating temperature: 0–40°C
- Storage: -20–70°C
- Humidity: 5–95% non-condensing
- EMC Compliance: Designed for industrial environments (CE class A equivalent)
- Quality Assurance: Factory-calibrated prior to shipment




### 9. Additional Information

Calibration:
- Eight variable resistors (VR1–VR8) for channel offset and full-scale adjustment.
- Factory-calibrated; user recalibration recommended every 6–12 months.
- Calibration utility included on software CD.

Software Utilities:
- 9812util.exe – Configuration, calibration, and functional testing tool.
- Programming Libraries:
- DOS: Borland C/C++ library
- Windows: DLLs for C/C++, Visual Basic, LabVIEW
- ActiveX: DAQBench components
- DASYLab: Graphical data acquisition and analysis

Warranty:
- Duration: 1-year limited warranty from date of purchase.
- Coverage: Defects in materials and workmanship.
- Exclusions: Damage from misuse, modification, or operation beyond specifications.
- Service: Return-to-factory repair or replacement; customer pays shipping if out of warranty.

Technical Support:
- Website: [www.adlinktech.com](http://www.adlinktech.com)
- Email: service@adlink.com.tw | nudaq@adlink.com.tw
- Phone: +886-2-82265877
- Fax: +886-2-82265717
- Address: 9F, No.166, Jian Yi Road, Chungho City, Taipei 235, Taiwan, R.O.C.

Maintenance:
- Keep connectors clean and free of dust.
- Avoid electrostatic discharge during handling.
- Store in anti-static packaging when not in use.

Software Updates:
- Periodic driver and library updates available via ADLINK’s website.
- Backward compatibility maintained across PCI-9810/9812/9812A series.




### Summary

The ADLINK PCI-9812A is a robust, high-speed, 12-bit, 4-channel simultaneous-sampling analog input card engineered for precision data acquisition in industrial and scientific environments. With its 20 MS/s sampling rate, large 128K-sample FIFO, flexible triggering and clocking options, and comprehensive software support, it delivers exceptional performance for real-time signal capture and analysis. Its PCI bus mastering DMA architecture ensures efficient data throughput, while its modular design and calibration features provide long-term reliability and accuracy. The PCI-9812A stands as a versatile and cost-effective solution for engineers and researchers requiring high-speed, high-resolution analog data acquisition on the PCI platform.
  • WD-DASK - Windows driver API for PCI/PXI-9820 and PXI-98xx Digitizer
  • SMB-BNC-1m - SMB to BNC cable 1m (PXI-9816/26/46)