- USB 2.0 High‑Speed Interface: Fully compliant with USB 2.0 specification, supporting both full‑speed (12 Mbps) and high‑speed (480 Mbps) operation. Enables direct connection to desktop or notebook PCs without internal expansion slots.
- Opto‑Isolated I/O: All digital input and output channels are optically isolated from the host PC, protecting against electrical noise and ground potential differences.
- 8 × Digital Inputs / 8 × Digital Outputs: TTL‑level, positive logic digital I/O lines suitable for industrial sensors, switches, and control signals.
- High‑Resolution A/D Conversion: 16‑bit analog‑to‑digital conversion with selectable input ranges (±10 V, ±5 V, 0–10 V, 0–5 V).
- High‑Speed Sampling: Typical conversion time of 10 µs per channel plus 20 µs overhead, enabling rapid data acquisition for control and monitoring.
- Large Onboard Buffer Memory: 256 K‑word (262,144 samples) FIFO or ring buffer memory allows continuous background sampling independent of PC CPU load.
- Compact Industrial Design: Small form factor (50.4 W × 64.7 D × 94 H mm) with integrated DIN‑rail mounting mechanism and optional magnetic or desktop installation.
- Bus Isolation: Complete isolation between USB bus and external I/O circuitry prevents host PC malfunction due to field noise or surges.
- Software‑Configurable Ranges: Input voltage ranges and sampling parameters are set entirely by software—no jumpers or manual calibration required.
- Cross‑Platform Driver Support: Includes license‑free Windows and Linux drivers, plus LabVIEW and MATLAB libraries for rapid integration into measurement systems.
- Expandable Architecture: Supports connection of up to three expansion modules (e.g., ADI12‑8(FIT)GY) for channel expansion while maintaining a single USB interface.
- Industrial Reliability: Designed for 0–50 °C operation, 10–90 % RH (non‑condensing), with robust connectors and over‑voltage protection (±20 V tolerance).
- Opto‑Isolated I/O: All digital input and output channels are optically isolated from the host PC, protecting against electrical noise and ground potential differences.
- 8 × Digital Inputs / 8 × Digital Outputs: TTL‑level, positive logic digital I/O lines suitable for industrial sensors, switches, and control signals.
- High‑Resolution A/D Conversion: 16‑bit analog‑to‑digital conversion with selectable input ranges (±10 V, ±5 V, 0–10 V, 0–5 V).
- High‑Speed Sampling: Typical conversion time of 10 µs per channel plus 20 µs overhead, enabling rapid data acquisition for control and monitoring.
- Large Onboard Buffer Memory: 256 K‑word (262,144 samples) FIFO or ring buffer memory allows continuous background sampling independent of PC CPU load.
- Compact Industrial Design: Small form factor (50.4 W × 64.7 D × 94 H mm) with integrated DIN‑rail mounting mechanism and optional magnetic or desktop installation.
- Bus Isolation: Complete isolation between USB bus and external I/O circuitry prevents host PC malfunction due to field noise or surges.
- Software‑Configurable Ranges: Input voltage ranges and sampling parameters are set entirely by software—no jumpers or manual calibration required.
- Cross‑Platform Driver Support: Includes license‑free Windows and Linux drivers, plus LabVIEW and MATLAB libraries for rapid integration into measurement systems.
- Expandable Architecture: Supports connection of up to three expansion modules (e.g., ADI12‑8(FIT)GY) for channel expansion while maintaining a single USB interface.
- Industrial Reliability: Designed for 0–50 °C operation, 10–90 % RH (non‑condensing), with robust connectors and over‑voltage protection (±20 V tolerance).
1. Product Overview
Product Name: DIO‑0808RN‑USB
Model / Article Number: DIO‑0808RN‑USB
Series: USB 2.0 Digital I/O Module (part of CONTEC’s Industrial Measurement and Control product family)
Manufacturer: CONTEC Co., Ltd. (Osaka, Japan)
Product Description: USB 2.0‑compliant, opto‑isolated 8‑channel digital input and 8‑channel digital output module with 16‑bit A/D capability, ±10 V/±5 V or 0–10 V/0–5 V input range, 256 K‑word data buffer, and compact DIN‑rail mountable housing (50.4 × 64.7 × 94 mm). Designed for PC‑based measurement, control, and automation systems requiring isolated digital I/O and analog acquisition via USB interface.
2. Key Features
- USB 2.0 High‑Speed Interface: Fully compliant with USB 2.0 specification, supporting both full‑speed (12 Mbps) and high‑speed (480 Mbps) operation. Enables direct connection to desktop or notebook PCs without internal expansion slots.
- Opto‑Isolated I/O: All digital input and output channels are optically isolated from the host PC, protecting against electrical noise and ground potential differences.
- 8 × Digital Inputs / 8 × Digital Outputs: TTL‑level, positive logic digital I/O lines suitable for industrial sensors, switches, and control signals.
- High‑Resolution A/D Conversion: 16‑bit analog‑to‑digital conversion with selectable input ranges (±10 V, ±5 V, 0–10 V, 0–5 V).
- High‑Speed Sampling: Typical conversion time of 10 µs per channel plus 20 µs overhead, enabling rapid data acquisition for control and monitoring.
- Large Onboard Buffer Memory: 256 K‑word (262,144 samples) FIFO or ring buffer memory allows continuous background sampling independent of PC CPU load.
- Compact Industrial Design: Small form factor (50.4 W × 64.7 D × 94 H mm) with integrated DIN‑rail mounting mechanism and optional magnetic or desktop installation.
- Bus Isolation: Complete isolation between USB bus and external I/O circuitry prevents host PC malfunction due to field noise or surges.
- Software‑Configurable Ranges: Input voltage ranges and sampling parameters are set entirely by software—no jumpers or manual calibration required.
- Cross‑Platform Driver Support: Includes license‑free Windows and Linux drivers, plus LabVIEW and MATLAB libraries for rapid integration into measurement systems.
- Expandable Architecture: Supports connection of up to three expansion modules (e.g., ADI12‑8(FIT)GY) for channel expansion while maintaining a single USB interface.
- Industrial Reliability: Designed for 0–50 °C operation, 10–90 % RH (non‑condensing), with robust connectors and over‑voltage protection (±20 V tolerance).
3. Technical Specifications
| Parameter | Specification |
|----------------|------------------|
| Digital Input Channels | 8 channels, opto‑isolated, TTL‑level (positive logic) |
| Digital Output Channels | 8 channels, opto‑isolated, TTL‑level (positive logic) |
| Analog Input Resolution | 16 bits |
| Input Ranges | Bipolar: ±10 V, ±5 V Unipolar: 0–10 V, 0–5 V |
| Maximum Input Voltage | ±20 V (protection limit) |
| Input Impedance | ≥ 1 MΩ |
| Conversion Speed | Voltage: 10 µs/ch + 20 µs overhead Current: 40 µs/ch + 20 µs overhead |
| Non‑Linearity Error | ±3 LSB typical |
| Data Buffer Memory | 256 K samples (FIFO or ring buffer selectable) |
| Sampling Timer Range | 10 µs – 1,073,741,824 µs (1 s ≈ 1 × 10⁶ µs) |
| USB Interface | USB 2.0 compliant, full‑speed (12 Mbps) / high‑speed (480 Mbps) |
| Power Supply | +5 V DC ± 5 %, 650 mA max (AC adapter POA‑AD22 included) |
| Isolation Method | Photo‑coupler isolation between USB bus and I/O circuitry |
| Operating Temperature | 0 – 50 °C |
| Operating Humidity | 10 – 90 % RH (non‑condensing) |
| Dimensions (W × D × H) | 50.4 × 64.7 × 94.0 mm (excluding protrusions) |
| Weight | Approx. 100 g |
| Mounting | 35 mm DIN‑rail (one‑touch mechanism) or desktop with rubber feet |
| Connectors | FK‑MC 0.5/12‑ST‑2.5 (Phoenix Contact), 2.5 mm pitch, AWG 28–20 wire |
| Maximum Modules per Bus | Up to 127 USB devices (including hubs) |
| Expansion Modules | Up to 3 × ADI12‑8(FIT)GY (8 channels each) |
| Compliance | USB 2.0 specification, CE mark applicable (industrial use) |
4. Functionality
The DIO‑0808RN‑USB operates as a USB‑connected data acquisition and control interface. It converts external analog or digital signals into digital data for PC‑based processing and can output digital control signals to external actuators or logic circuits.
- Operation Principle:
The module’s internal microprocessor manages A/D conversion and buffering. Analog or digital inputs are sampled at user‑defined intervals, stored in onboard memory, and transferred to the host PC via USB. Outputs are updated through software commands or timed sequences.
- Use Cases:
- Industrial automation and process monitoring
- Laboratory data acquisition and test benches
- Portable measurement systems using notebook PCs
- Embedded control for equipment diagnostics
- Educational and research instrumentation requiring isolated I/O
- Compatibility:
Works with any PC supporting USB 2.0/1.1 ports under Windows 98/Me/2000/XP or Linux. Compatible with CONTEC’s API‑USBP(WDM) driver library, LabVIEW VI‑DAQ, and MATLAB ML‑DAQ toolkits.
5. Components & Accessories
Included Items:
- DIO‑0808RN‑USB main module
- AC adapter (POA‑AD22, 90–264 V AC → 5 V DC 2 A)
- USB 2.0 cable (1.8 m)
- Protective rubber feet × 4
- Mounting magnets × 2
- Interface connector plugs (FK‑MC 0.5/12‑ST‑2.5)
- User’s Guide / First‑Step Guide
- CD‑ROM (API‑USBP(WDM) driver and utilities)
Optional Accessories:
- Expansion analog input modules ADI12‑8(FIT)GY (8 ch each)
- DIN‑rail power supplies: POW‑AD13GY, POW‑AD22GY, POW‑AD25GY, POW‑DD10GY, POW‑DD43GY
- Additional cables and terminal blocks (EPD‑37A, ATP‑8L, etc.)
- DIN‑rail adapter DIN‑ADP1 (for panel mounting)
Connectors:
12‑pin screwless terminal block for analog/digital I/O; 5 V DC input terminal (Vi+, Vi, FG); USB Type‑B port for host connection.
6. Installation & Setup
- Power Requirements:
Operates from external +5 V DC supply (650 mA max). Always use the bundled AC adapter or approved DIN‑rail power supply.
- Mounting Options:
- DIN‑rail: One‑touch mounting on 35 mm rail with locking hook.
- Desktop: Attach rubber feet for horizontal placement.
- Magnetic: Use included magnets for temporary mounting on metal surfaces.
- Connection Procedure:
1. Connect external power supply to +5 V input terminal.
2. Connect USB cable to PC USB port.
3. Install driver (API‑USBP(WDM)) from CD‑ROM.
4. Configure device name and properties via Windows Device Manager.
5. Verify operation using the included diagnostic utility.
- Module ID Setting:
Rotary switches (x16 and x1) set unique Module ID (00–7Fh). Factory default = 00. Required only when multiple modules of same model are connected.
- Expansion Module Connection:
Up to three ADI12‑8(FIT)GY modules can be stack‑connected using locking hooks and Device ID rotary switches (1–3). Total input channels = 32.
- Grounding & Noise Precautions:
Connect FG terminal to earth ground in noisy environments. Attach ferrite cores to USB and power cables to reduce EMI.
- Environmental Conditions:
Operate in 0–50 °C, 10–90 % RH (non‑condensing). Avoid exposure to corrosive gases or excessive dust.
7. Performance & Capabilities
- Sampling Performance:
- A/D conversion time: 10 µs per channel + 20 µs overhead.
- Minimum sampling period: ≈ 600 µs (1 ch) to 2 ms (32 ch with expansion).
- Internal CPU handles sampling independently of host PC load.
- Buffer Operation:
256 K‑word memory supports continuous sampling without data loss. Data transfer to PC occurs in blocks via USB.
- Trigger Modes:
- Software Trigger: Start/stop controlled by API commands.
- Level Trigger: Sampling initiated by analog signal crossing a set threshold (upward or downward slope).
- Accuracy:
±3 LSB typical linearity error; ±20 V input protection.
- Isolation & Protection:
Photo‑coupler isolation between USB bus and I/O circuits; each channel protected against over‑voltage and transient noise.
- Capacity & Expansion:
Base unit provides 8 DI + 8 DO channels; expandable to 32 analog inputs with three FIT modules.
- Limitations:
Channels within a module share common analog ground (not individually isolated). Modules do not synchronize sampling across multiple USB devices.
8. Standards & Compliance
- USB Compliance: Conforms to USB 2.0 specification (Full Speed 12 Mbps / High Speed 480 Mbps).
- Electrical Safety: Bus and signal isolation via photo‑couplers and DC/DC converter.
- Environmental: Designed for industrial temperature range (0–50 °C).
- EMC / CE Mark: Meets industrial EMC requirements for CE marking (when used with shielded cables and grounding as specified).
- RoHS Compliance: Manufactured in accordance with RoHS directives for hazardous substance control.
- Software Standards: API‑USBP(WDM) driver complies with Microsoft Win32 API conventions; supports LabVIEW VI‑DAQ and MATLAB ML‑DAQ interfaces.
9. Additional Information
- Warranty: One‑year limited warranty covering defects in materials and workmanship. Excludes damage from misuse or modification.
- Support & Service: Technical support available via CONTEC regional offices and online portal (www.contec.com). Free driver and firmware updates downloadable from the website.
- Maintenance: Inspect ventilation slits and connectors periodically; keep free of dust and debris. Do not open the enclosure or modify hardware.
- Firmware Updates: Modules can be upgraded via USB using the Firmware Upgrade Tool provided with API‑USBP(WDM). Set Module ID to FFh for update mode.
- Software Tools:
- API‑USBP(WDM): Win32 DLL library for C/C++/VB/.NET development.
- Hyper Logger: Graphical data logging utility for real‑time acquisition and file storage.
- Diagnostic Program: Hardware test utility for channel verification and firmware version check.
- LabVIEW VI‑DAQ / MATLAB ML‑DAQ: Libraries for integration with scientific software environments.
- Safety Precautions: Operate in non‑flammable environments; avoid impact or bending of module; disconnect power before wiring or adding expansion modules.
- Storage & Disposal: Store in dry conditions (0–40 °C); dispose according to local electronic waste regulations.
- Firmware & Driver Updates: Available free of charge from CONTEC’s download center. Drivers are license‑free for both development and runtime use.
- Customer Support Contacts:
- Japan: www.contec.co.jp
- Global: www.contec.com
- China: www.contec.com.cn
Summary
The CONTEC DIO‑0808RN‑USB is a compact, high‑performance USB 2.0 digital I/O and analog acquisition module engineered for industrial and laboratory measurement systems. It combines 8 isolated digital inputs, 8 isolated digital outputs, and 16‑bit analog input capability within a rugged, bus‑isolated enclosure. With a 256 K‑word buffer, 10 µs/channel conversion speed, and comprehensive software support for Windows, Linux, LabVIEW, and MATLAB, it enables reliable, high‑speed data acquisition and control through a simple USB connection. Its modular expandability, DIN‑rail mounting, and robust isolation make it ideal for portable or embedded PC‑based automation and monitoring applications.
Product Name: DIO‑0808RN‑USB
Model / Article Number: DIO‑0808RN‑USB
Series: USB 2.0 Digital I/O Module (part of CONTEC’s Industrial Measurement and Control product family)
Manufacturer: CONTEC Co., Ltd. (Osaka, Japan)
Product Description: USB 2.0‑compliant, opto‑isolated 8‑channel digital input and 8‑channel digital output module with 16‑bit A/D capability, ±10 V/±5 V or 0–10 V/0–5 V input range, 256 K‑word data buffer, and compact DIN‑rail mountable housing (50.4 × 64.7 × 94 mm). Designed for PC‑based measurement, control, and automation systems requiring isolated digital I/O and analog acquisition via USB interface.
2. Key Features
- USB 2.0 High‑Speed Interface: Fully compliant with USB 2.0 specification, supporting both full‑speed (12 Mbps) and high‑speed (480 Mbps) operation. Enables direct connection to desktop or notebook PCs without internal expansion slots.
- Opto‑Isolated I/O: All digital input and output channels are optically isolated from the host PC, protecting against electrical noise and ground potential differences.
- 8 × Digital Inputs / 8 × Digital Outputs: TTL‑level, positive logic digital I/O lines suitable for industrial sensors, switches, and control signals.
- High‑Resolution A/D Conversion: 16‑bit analog‑to‑digital conversion with selectable input ranges (±10 V, ±5 V, 0–10 V, 0–5 V).
- High‑Speed Sampling: Typical conversion time of 10 µs per channel plus 20 µs overhead, enabling rapid data acquisition for control and monitoring.
- Large Onboard Buffer Memory: 256 K‑word (262,144 samples) FIFO or ring buffer memory allows continuous background sampling independent of PC CPU load.
- Compact Industrial Design: Small form factor (50.4 W × 64.7 D × 94 H mm) with integrated DIN‑rail mounting mechanism and optional magnetic or desktop installation.
- Bus Isolation: Complete isolation between USB bus and external I/O circuitry prevents host PC malfunction due to field noise or surges.
- Software‑Configurable Ranges: Input voltage ranges and sampling parameters are set entirely by software—no jumpers or manual calibration required.
- Cross‑Platform Driver Support: Includes license‑free Windows and Linux drivers, plus LabVIEW and MATLAB libraries for rapid integration into measurement systems.
- Expandable Architecture: Supports connection of up to three expansion modules (e.g., ADI12‑8(FIT)GY) for channel expansion while maintaining a single USB interface.
- Industrial Reliability: Designed for 0–50 °C operation, 10–90 % RH (non‑condensing), with robust connectors and over‑voltage protection (±20 V tolerance).
3. Technical Specifications
| Parameter | Specification |
|----------------|------------------|
| Digital Input Channels | 8 channels, opto‑isolated, TTL‑level (positive logic) |
| Digital Output Channels | 8 channels, opto‑isolated, TTL‑level (positive logic) |
| Analog Input Resolution | 16 bits |
| Input Ranges | Bipolar: ±10 V, ±5 V Unipolar: 0–10 V, 0–5 V |
| Maximum Input Voltage | ±20 V (protection limit) |
| Input Impedance | ≥ 1 MΩ |
| Conversion Speed | Voltage: 10 µs/ch + 20 µs overhead Current: 40 µs/ch + 20 µs overhead |
| Non‑Linearity Error | ±3 LSB typical |
| Data Buffer Memory | 256 K samples (FIFO or ring buffer selectable) |
| Sampling Timer Range | 10 µs – 1,073,741,824 µs (1 s ≈ 1 × 10⁶ µs) |
| USB Interface | USB 2.0 compliant, full‑speed (12 Mbps) / high‑speed (480 Mbps) |
| Power Supply | +5 V DC ± 5 %, 650 mA max (AC adapter POA‑AD22 included) |
| Isolation Method | Photo‑coupler isolation between USB bus and I/O circuitry |
| Operating Temperature | 0 – 50 °C |
| Operating Humidity | 10 – 90 % RH (non‑condensing) |
| Dimensions (W × D × H) | 50.4 × 64.7 × 94.0 mm (excluding protrusions) |
| Weight | Approx. 100 g |
| Mounting | 35 mm DIN‑rail (one‑touch mechanism) or desktop with rubber feet |
| Connectors | FK‑MC 0.5/12‑ST‑2.5 (Phoenix Contact), 2.5 mm pitch, AWG 28–20 wire |
| Maximum Modules per Bus | Up to 127 USB devices (including hubs) |
| Expansion Modules | Up to 3 × ADI12‑8(FIT)GY (8 channels each) |
| Compliance | USB 2.0 specification, CE mark applicable (industrial use) |
4. Functionality
The DIO‑0808RN‑USB operates as a USB‑connected data acquisition and control interface. It converts external analog or digital signals into digital data for PC‑based processing and can output digital control signals to external actuators or logic circuits.
- Operation Principle:
The module’s internal microprocessor manages A/D conversion and buffering. Analog or digital inputs are sampled at user‑defined intervals, stored in onboard memory, and transferred to the host PC via USB. Outputs are updated through software commands or timed sequences.
- Use Cases:
- Industrial automation and process monitoring
- Laboratory data acquisition and test benches
- Portable measurement systems using notebook PCs
- Embedded control for equipment diagnostics
- Educational and research instrumentation requiring isolated I/O
- Compatibility:
Works with any PC supporting USB 2.0/1.1 ports under Windows 98/Me/2000/XP or Linux. Compatible with CONTEC’s API‑USBP(WDM) driver library, LabVIEW VI‑DAQ, and MATLAB ML‑DAQ toolkits.
5. Components & Accessories
Included Items:
- DIO‑0808RN‑USB main module
- AC adapter (POA‑AD22, 90–264 V AC → 5 V DC 2 A)
- USB 2.0 cable (1.8 m)
- Protective rubber feet × 4
- Mounting magnets × 2
- Interface connector plugs (FK‑MC 0.5/12‑ST‑2.5)
- User’s Guide / First‑Step Guide
- CD‑ROM (API‑USBP(WDM) driver and utilities)
Optional Accessories:
- Expansion analog input modules ADI12‑8(FIT)GY (8 ch each)
- DIN‑rail power supplies: POW‑AD13GY, POW‑AD22GY, POW‑AD25GY, POW‑DD10GY, POW‑DD43GY
- Additional cables and terminal blocks (EPD‑37A, ATP‑8L, etc.)
- DIN‑rail adapter DIN‑ADP1 (for panel mounting)
Connectors:
12‑pin screwless terminal block for analog/digital I/O; 5 V DC input terminal (Vi+, Vi, FG); USB Type‑B port for host connection.
6. Installation & Setup
- Power Requirements:
Operates from external +5 V DC supply (650 mA max). Always use the bundled AC adapter or approved DIN‑rail power supply.
- Mounting Options:
- DIN‑rail: One‑touch mounting on 35 mm rail with locking hook.
- Desktop: Attach rubber feet for horizontal placement.
- Magnetic: Use included magnets for temporary mounting on metal surfaces.
- Connection Procedure:
1. Connect external power supply to +5 V input terminal.
2. Connect USB cable to PC USB port.
3. Install driver (API‑USBP(WDM)) from CD‑ROM.
4. Configure device name and properties via Windows Device Manager.
5. Verify operation using the included diagnostic utility.
- Module ID Setting:
Rotary switches (x16 and x1) set unique Module ID (00–7Fh). Factory default = 00. Required only when multiple modules of same model are connected.
- Expansion Module Connection:
Up to three ADI12‑8(FIT)GY modules can be stack‑connected using locking hooks and Device ID rotary switches (1–3). Total input channels = 32.
- Grounding & Noise Precautions:
Connect FG terminal to earth ground in noisy environments. Attach ferrite cores to USB and power cables to reduce EMI.
- Environmental Conditions:
Operate in 0–50 °C, 10–90 % RH (non‑condensing). Avoid exposure to corrosive gases or excessive dust.
7. Performance & Capabilities
- Sampling Performance:
- A/D conversion time: 10 µs per channel + 20 µs overhead.
- Minimum sampling period: ≈ 600 µs (1 ch) to 2 ms (32 ch with expansion).
- Internal CPU handles sampling independently of host PC load.
- Buffer Operation:
256 K‑word memory supports continuous sampling without data loss. Data transfer to PC occurs in blocks via USB.
- Trigger Modes:
- Software Trigger: Start/stop controlled by API commands.
- Level Trigger: Sampling initiated by analog signal crossing a set threshold (upward or downward slope).
- Accuracy:
±3 LSB typical linearity error; ±20 V input protection.
- Isolation & Protection:
Photo‑coupler isolation between USB bus and I/O circuits; each channel protected against over‑voltage and transient noise.
- Capacity & Expansion:
Base unit provides 8 DI + 8 DO channels; expandable to 32 analog inputs with three FIT modules.
- Limitations:
Channels within a module share common analog ground (not individually isolated). Modules do not synchronize sampling across multiple USB devices.
8. Standards & Compliance
- USB Compliance: Conforms to USB 2.0 specification (Full Speed 12 Mbps / High Speed 480 Mbps).
- Electrical Safety: Bus and signal isolation via photo‑couplers and DC/DC converter.
- Environmental: Designed for industrial temperature range (0–50 °C).
- EMC / CE Mark: Meets industrial EMC requirements for CE marking (when used with shielded cables and grounding as specified).
- RoHS Compliance: Manufactured in accordance with RoHS directives for hazardous substance control.
- Software Standards: API‑USBP(WDM) driver complies with Microsoft Win32 API conventions; supports LabVIEW VI‑DAQ and MATLAB ML‑DAQ interfaces.
9. Additional Information
- Warranty: One‑year limited warranty covering defects in materials and workmanship. Excludes damage from misuse or modification.
- Support & Service: Technical support available via CONTEC regional offices and online portal (www.contec.com). Free driver and firmware updates downloadable from the website.
- Maintenance: Inspect ventilation slits and connectors periodically; keep free of dust and debris. Do not open the enclosure or modify hardware.
- Firmware Updates: Modules can be upgraded via USB using the Firmware Upgrade Tool provided with API‑USBP(WDM). Set Module ID to FFh for update mode.
- Software Tools:
- API‑USBP(WDM): Win32 DLL library for C/C++/VB/.NET development.
- Hyper Logger: Graphical data logging utility for real‑time acquisition and file storage.
- Diagnostic Program: Hardware test utility for channel verification and firmware version check.
- LabVIEW VI‑DAQ / MATLAB ML‑DAQ: Libraries for integration with scientific software environments.
- Safety Precautions: Operate in non‑flammable environments; avoid impact or bending of module; disconnect power before wiring or adding expansion modules.
- Storage & Disposal: Store in dry conditions (0–40 °C); dispose according to local electronic waste regulations.
- Firmware & Driver Updates: Available free of charge from CONTEC’s download center. Drivers are license‑free for both development and runtime use.
- Customer Support Contacts:
- Japan: www.contec.co.jp
- Global: www.contec.com
- China: www.contec.com.cn
Summary
The CONTEC DIO‑0808RN‑USB is a compact, high‑performance USB 2.0 digital I/O and analog acquisition module engineered for industrial and laboratory measurement systems. It combines 8 isolated digital inputs, 8 isolated digital outputs, and 16‑bit analog input capability within a rugged, bus‑isolated enclosure. With a 256 K‑word buffer, 10 µs/channel conversion speed, and comprehensive software support for Windows, Linux, LabVIEW, and MATLAB, it enables reliable, high‑speed data acquisition and control through a simple USB connection. Its modular expandability, DIN‑rail mounting, and robust isolation make it ideal for portable or embedded PC‑based automation and monitoring applications.
-
G_analog_io.pdf
PDF Catalog
-
ADI12-8(USB).pdf
Manual
No accessories available.