LOOKING FOR THE RIGHT
INDUSTRIAL SOLUTION?
Discover embedded, communication and automation solutions tailored to your application.
- 6 RTD Input Channels: Supports Pt50, Pt100, Pt200, Pt500, and Pt1000 sensors for precise temperature measurement.
- High Sampling Rate: 12 samples per second across all channels, ensuring real-time data acquisition.
- 16-bit Resolution: Provides high accuracy and fine measurement granularity.
- Built-in 2-Port Ethernet Switch: Enables daisy-chain topology, reducing the need for external switches and simplifying wiring.
- Active OPC Server Lite Support: Push-based architecture for SCADA integration, reducing network traffic by up to 80% and improving response time by up to 7× compared to traditional polling.
- User-defined Modbus/TCP Addressing: Allows flexible mapping of I/O addresses for seamless integration with existing Modbus systems.
- MXIO Library Support: Compatible with Windows, WinCE (VB/VC.NET), and Linux (C API) for custom application development.
- Web-based Configuration: Built-in web console with import/export functionality for easy setup and replication.
- Peer-to-Peer Communication: Direct I/O signal transmission between devices without a central controller.
- Compact and Lightweight Design: DIN-rail and wall-mountable enclosure with stress-relief wiring support.
- Wide Operating Temperature Range: Standard model supports -10 to +60°C; optional “-T” model supports -40 to +75°C.
- Industrial-grade Reliability: 1.5 kV Ethernet isolation, 3 kV I/O isolation, and compliance with IEC 61000-4/6 standards.
- High Sampling Rate: 12 samples per second across all channels, ensuring real-time data acquisition.
- 16-bit Resolution: Provides high accuracy and fine measurement granularity.
- Built-in 2-Port Ethernet Switch: Enables daisy-chain topology, reducing the need for external switches and simplifying wiring.
- Active OPC Server Lite Support: Push-based architecture for SCADA integration, reducing network traffic by up to 80% and improving response time by up to 7× compared to traditional polling.
- User-defined Modbus/TCP Addressing: Allows flexible mapping of I/O addresses for seamless integration with existing Modbus systems.
- MXIO Library Support: Compatible with Windows, WinCE (VB/VC.NET), and Linux (C API) for custom application development.
- Web-based Configuration: Built-in web console with import/export functionality for easy setup and replication.
- Peer-to-Peer Communication: Direct I/O signal transmission between devices without a central controller.
- Compact and Lightweight Design: DIN-rail and wall-mountable enclosure with stress-relief wiring support.
- Wide Operating Temperature Range: Standard model supports -10 to +60°C; optional “-T” model supports -40 to +75°C.
- Industrial-grade Reliability: 1.5 kV Ethernet isolation, 3 kV I/O isolation, and compliance with IEC 61000-4/6 standards.
Comprehensive Product Summary: Moxa ioLogik E1260 Ethernet Remote I/O Module
### 1. Product Overview
Product Name: ioLogik E1260
Model: E1260
Series: ioLogik E1200 Series – Remote Ethernet I/O with 2-port Ethernet Switch
Article Number: E1260
Manufacturer: Moxa Inc.
The Moxa ioLogik E1260 is an industrial-grade Ethernet remote I/O module designed for distributed temperature measurement and monitoring applications. It supports six RTD (Resistance Temperature Detector) input channels and integrates dual 10/100 Mbps Ethernet ports with an embedded switch for daisy-chain network topologies. The device is part of Moxa’s ioLogik E1200 family, which provides modular, intelligent, and network-efficient I/O solutions for industrial automation, SCADA integration, and remote data acquisition.
### 2. Key Features
- 6 RTD Input Channels: Supports Pt50, Pt100, Pt200, Pt500, and Pt1000 sensors for precise temperature measurement.
- High Sampling Rate: 12 samples per second across all channels, ensuring real-time data acquisition.
- 16-bit Resolution: Provides high accuracy and fine measurement granularity.
- Built-in 2-Port Ethernet Switch: Enables daisy-chain topology, reducing the need for external switches and simplifying wiring.
- Active OPC Server Lite Support: Push-based architecture for SCADA integration, reducing network traffic by up to 80% and improving response time by up to 7× compared to traditional polling.
- User-defined Modbus/TCP Addressing: Allows flexible mapping of I/O addresses for seamless integration with existing Modbus systems.
- MXIO Library Support: Compatible with Windows, WinCE (VB/VC.NET), and Linux (C API) for custom application development.
- Web-based Configuration: Built-in web console with import/export functionality for easy setup and replication.
- Peer-to-Peer Communication: Direct I/O signal transmission between devices without a central controller.
- Compact and Lightweight Design: DIN-rail and wall-mountable enclosure with stress-relief wiring support.
- Wide Operating Temperature Range: Standard model supports -10 to +60°C; optional “-T” model supports -40 to +75°C.
- Industrial-grade Reliability: 1.5 kV Ethernet isolation, 3 kV I/O isolation, and compliance with IEC 61000-4/6 standards.
### 3. Technical Specifications
RTD Input
- Channels: 6 differential RTD inputs
- Supported Sensors: Pt50, Pt100, Pt200, Pt500, Pt1000
- Resistance Range: 10 Ω, 20 Ω, 100 Ω
- Resolution: 16 bits
- Sampling Rate: 12 samples/sec (all channels)
- Accuracy: ±0.1% FSR @ 25°C; ±0.3% FSR @ -10 to 60°C
- Input Impedance: 625 kΩ
Ethernet Interface
- Ports: 2 × 10/100 Mbps RJ45 ports (embedded switch)
- Isolation Protection: 1.5 kV magnetic isolation
- Supported Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP
Power Requirements
- Input Voltage: 24 VDC nominal (12–36 VDC range)
- Power Consumption: 110 mA typical @ 24 VDC
Physical Characteristics
- Wiring: Screw clamp terminal, max. 14 AWG
- Dimensions: 27.8 × 124 × 84 mm (1.09 × 4.88 × 3.31 in)
- Weight: <200 g (typical 179 g)
- Mounting: DIN-rail or wall mount
- Enclosure: Industrial-grade plastic housing with stress-relief connector
Environmental Limits
- Operating Temperature: -10 to +60°C (standard); -40 to +75°C (E1260-T model)
- Storage Temperature: -40 to +85°C
- Humidity: 5–95% RH (non-condensing)
Reliability
- MTBF: 660,260 hours (Telcordia SR-332, Bellcore standard)
### 4. Functionality
The ioLogik E1260 functions as a remote Ethernet I/O device for temperature monitoring using RTD sensors. Each of its six channels can independently measure resistance or temperature values from connected RTDs. The module converts analog resistance signals into digital temperature data, which can be transmitted over Ethernet using Modbus/TCP or Moxa’s Active OPC Server Lite.
Use Cases and Applications:
- Industrial process temperature monitoring
- Factory automation and environmental control
- Building management systems (HVAC)
- Energy and utility monitoring
- Tunnel and transportation infrastructure
- Remote cabinet and enclosure temperature supervision
Compatibility:
- SCADA and HMI systems supporting OPC DA 1.0a/2.0/3.0
- Modbus/TCP-compatible PLCs and controllers
- Moxa Active OPC Server Lite and MXIO libraries for custom integration
### 5. Components & Accessories
Included Items:
- ioLogik E1260 Ethernet Remote I/O module
- Documentation and software CD (includes ioSearch utility and Active OPC Server Lite)
- Quick Installation Guide
Optional Accessories:
- DIN-rail mounting kit (included by default)
- Wall-mount brackets
- External 24 VDC power supply
- Ethernet cables (Cat5e or higher)
Connectors:
- Dual RJ45 Ethernet ports (10/100BaseT(X))
- Screw terminal blocks for RTD inputs and power connections
### 6. Installation & Setup
Power Connection:
Connect a 12–36 VDC power source to the terminal block on the top panel. The Power LED (amber) indicates active power.
Grounding:
A dedicated grounding terminal is provided for earth connection to minimize electrical noise and ensure safety.
Network Connection:
Two RJ45 ports allow daisy-chaining multiple ioLogik units or connecting to other Ethernet devices (e.g., PLCs, IP cameras). Default IP: 192.168.127.254 / Subnet: 255.255.255.0.
Configuration Tools:
- Web Console: Browser-based interface for network, I/O, and system settings.
- ioSearch Utility: Windows-based discovery and configuration tool for locating and managing multiple devices.
- Active OPC Server Lite: For SCADA integration and tag generation.
Mounting Options:
- DIN-rail (standard)
- Wall-mount (optional)
Factory Reset:
Hold the reset button for 5 seconds or use ioSearch/web console “Load Factory Default” option.
### 7. Performance & Capabilities
Measurement Performance:
- 16-bit resolution ensures precise temperature readings.
- 12 samples/sec across all channels for real-time monitoring.
- ±0.1% FSR accuracy at room temperature.
Network Performance:
- Dual-port Ethernet switch supports daisy-chain topology, reducing cabling and switch costs.
- Active OPC push-based communication reduces network bandwidth by up to 80%.
- I/O response time up to 7× faster than traditional polling-based systems.
Capacity & Scalability:
- Supports up to 6 RTD channels per module.
- Multiple modules can be cascaded via Ethernet for large-scale distributed systems.
- Peer-to-peer mapping supports up to 50 rules for direct I/O signal exchange between devices.
Limitations:
- Designed for RTD sensors only (no thermocouple support; use E1262 for TC).
- Requires 24 VDC power supply.
- Limited to 12 samples/sec aggregate rate.
### 8. Standards & Compliance
Safety and EMC:
- Safety: UL 508 (Industrial Control Equipment)
- EMI: FCC Part 15 Subpart B Class A, CISPR EN55022 Class A
- EMS: IEC 61000-4, IEC 61000-6 (industrial immunity standards)
- Shock: IEC 60068-2-27
- Vibration: IEC 60068-2-6
- Freefall: IEC 60068-2-32
Environmental Compliance:
- RoHS-compliant materials
- CE-marked for European markets
Network Standards:
- IEEE 802.3 10/100BaseT(X) Ethernet
- Modbus/TCP protocol compliance
### 9. Additional Information
Warranty:
- Standard Warranty: 5 years (E1260 and E1260-T models)
- Relay-based models (E1214 only): 2 years due to relay lifetime limitations
Support & Maintenance:
- Firmware updates available via web console or ioSearch utility.
- Configuration import/export for easy replication across multiple units.
- Technical support available through Moxa’s global support network:
- Americas: +1-888-669-2872
- Europe: +49-89-3700399-0
- Asia-Pacific: +886-2-8919-1230
- China: +86-21-5258-9955
- Online Support: [www.moxa.com/support](https://www.moxa.com/support)
Maintenance Recommendations:
- Periodically verify sensor calibration using the built-in RTD calibration function (30 seconds per channel).
- Inspect wiring and grounding connections for mechanical stress or corrosion.
- Keep firmware updated to ensure compatibility with the latest SCADA and OPC standards.
Software Ecosystem:
- Active OPC Server Lite: Free push-based OPC DA 3.0 server for SCADA integration.
- MXIO Library: API for Windows and Linux for custom application development.
- ioSearch Utility: Device discovery, IP configuration, and firmware management.
Firmware & Configuration Management:
- Web-based firmware upgrade capability.
- Import/export configuration files for backup or deployment.
- Peer-to-peer and safe-mode configuration for fail-safe operation.
### Summary
The Moxa ioLogik E1260 is a compact, high-precision Ethernet remote I/O module optimized for temperature monitoring using RTD sensors. It combines industrial reliability, flexible networking, and intelligent communication features to simplify distributed data acquisition in automation environments. With its dual Ethernet ports, 16-bit resolution, and support for Moxa’s Active OPC Server Lite, the E1260 delivers efficient, scalable, and low-latency integration into SCADA and control systems. Its rugged design, wide temperature tolerance, and long MTBF make it ideal for harsh industrial and infrastructure applications requiring dependable, real-time temperature data over Ethernet networks.
### 1. Product Overview
Product Name: ioLogik E1260
Model: E1260
Series: ioLogik E1200 Series – Remote Ethernet I/O with 2-port Ethernet Switch
Article Number: E1260
Manufacturer: Moxa Inc.
The Moxa ioLogik E1260 is an industrial-grade Ethernet remote I/O module designed for distributed temperature measurement and monitoring applications. It supports six RTD (Resistance Temperature Detector) input channels and integrates dual 10/100 Mbps Ethernet ports with an embedded switch for daisy-chain network topologies. The device is part of Moxa’s ioLogik E1200 family, which provides modular, intelligent, and network-efficient I/O solutions for industrial automation, SCADA integration, and remote data acquisition.
### 2. Key Features
- 6 RTD Input Channels: Supports Pt50, Pt100, Pt200, Pt500, and Pt1000 sensors for precise temperature measurement.
- High Sampling Rate: 12 samples per second across all channels, ensuring real-time data acquisition.
- 16-bit Resolution: Provides high accuracy and fine measurement granularity.
- Built-in 2-Port Ethernet Switch: Enables daisy-chain topology, reducing the need for external switches and simplifying wiring.
- Active OPC Server Lite Support: Push-based architecture for SCADA integration, reducing network traffic by up to 80% and improving response time by up to 7× compared to traditional polling.
- User-defined Modbus/TCP Addressing: Allows flexible mapping of I/O addresses for seamless integration with existing Modbus systems.
- MXIO Library Support: Compatible with Windows, WinCE (VB/VC.NET), and Linux (C API) for custom application development.
- Web-based Configuration: Built-in web console with import/export functionality for easy setup and replication.
- Peer-to-Peer Communication: Direct I/O signal transmission between devices without a central controller.
- Compact and Lightweight Design: DIN-rail and wall-mountable enclosure with stress-relief wiring support.
- Wide Operating Temperature Range: Standard model supports -10 to +60°C; optional “-T” model supports -40 to +75°C.
- Industrial-grade Reliability: 1.5 kV Ethernet isolation, 3 kV I/O isolation, and compliance with IEC 61000-4/6 standards.
### 3. Technical Specifications
RTD Input
- Channels: 6 differential RTD inputs
- Supported Sensors: Pt50, Pt100, Pt200, Pt500, Pt1000
- Resistance Range: 10 Ω, 20 Ω, 100 Ω
- Resolution: 16 bits
- Sampling Rate: 12 samples/sec (all channels)
- Accuracy: ±0.1% FSR @ 25°C; ±0.3% FSR @ -10 to 60°C
- Input Impedance: 625 kΩ
Ethernet Interface
- Ports: 2 × 10/100 Mbps RJ45 ports (embedded switch)
- Isolation Protection: 1.5 kV magnetic isolation
- Supported Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP
Power Requirements
- Input Voltage: 24 VDC nominal (12–36 VDC range)
- Power Consumption: 110 mA typical @ 24 VDC
Physical Characteristics
- Wiring: Screw clamp terminal, max. 14 AWG
- Dimensions: 27.8 × 124 × 84 mm (1.09 × 4.88 × 3.31 in)
- Weight: <200 g (typical 179 g)
- Mounting: DIN-rail or wall mount
- Enclosure: Industrial-grade plastic housing with stress-relief connector
Environmental Limits
- Operating Temperature: -10 to +60°C (standard); -40 to +75°C (E1260-T model)
- Storage Temperature: -40 to +85°C
- Humidity: 5–95% RH (non-condensing)
Reliability
- MTBF: 660,260 hours (Telcordia SR-332, Bellcore standard)
### 4. Functionality
The ioLogik E1260 functions as a remote Ethernet I/O device for temperature monitoring using RTD sensors. Each of its six channels can independently measure resistance or temperature values from connected RTDs. The module converts analog resistance signals into digital temperature data, which can be transmitted over Ethernet using Modbus/TCP or Moxa’s Active OPC Server Lite.
Use Cases and Applications:
- Industrial process temperature monitoring
- Factory automation and environmental control
- Building management systems (HVAC)
- Energy and utility monitoring
- Tunnel and transportation infrastructure
- Remote cabinet and enclosure temperature supervision
Compatibility:
- SCADA and HMI systems supporting OPC DA 1.0a/2.0/3.0
- Modbus/TCP-compatible PLCs and controllers
- Moxa Active OPC Server Lite and MXIO libraries for custom integration
### 5. Components & Accessories
Included Items:
- ioLogik E1260 Ethernet Remote I/O module
- Documentation and software CD (includes ioSearch utility and Active OPC Server Lite)
- Quick Installation Guide
Optional Accessories:
- DIN-rail mounting kit (included by default)
- Wall-mount brackets
- External 24 VDC power supply
- Ethernet cables (Cat5e or higher)
Connectors:
- Dual RJ45 Ethernet ports (10/100BaseT(X))
- Screw terminal blocks for RTD inputs and power connections
### 6. Installation & Setup
Power Connection:
Connect a 12–36 VDC power source to the terminal block on the top panel. The Power LED (amber) indicates active power.
Grounding:
A dedicated grounding terminal is provided for earth connection to minimize electrical noise and ensure safety.
Network Connection:
Two RJ45 ports allow daisy-chaining multiple ioLogik units or connecting to other Ethernet devices (e.g., PLCs, IP cameras). Default IP: 192.168.127.254 / Subnet: 255.255.255.0.
Configuration Tools:
- Web Console: Browser-based interface for network, I/O, and system settings.
- ioSearch Utility: Windows-based discovery and configuration tool for locating and managing multiple devices.
- Active OPC Server Lite: For SCADA integration and tag generation.
Mounting Options:
- DIN-rail (standard)
- Wall-mount (optional)
Factory Reset:
Hold the reset button for 5 seconds or use ioSearch/web console “Load Factory Default” option.
### 7. Performance & Capabilities
Measurement Performance:
- 16-bit resolution ensures precise temperature readings.
- 12 samples/sec across all channels for real-time monitoring.
- ±0.1% FSR accuracy at room temperature.
Network Performance:
- Dual-port Ethernet switch supports daisy-chain topology, reducing cabling and switch costs.
- Active OPC push-based communication reduces network bandwidth by up to 80%.
- I/O response time up to 7× faster than traditional polling-based systems.
Capacity & Scalability:
- Supports up to 6 RTD channels per module.
- Multiple modules can be cascaded via Ethernet for large-scale distributed systems.
- Peer-to-peer mapping supports up to 50 rules for direct I/O signal exchange between devices.
Limitations:
- Designed for RTD sensors only (no thermocouple support; use E1262 for TC).
- Requires 24 VDC power supply.
- Limited to 12 samples/sec aggregate rate.
### 8. Standards & Compliance
Safety and EMC:
- Safety: UL 508 (Industrial Control Equipment)
- EMI: FCC Part 15 Subpart B Class A, CISPR EN55022 Class A
- EMS: IEC 61000-4, IEC 61000-6 (industrial immunity standards)
- Shock: IEC 60068-2-27
- Vibration: IEC 60068-2-6
- Freefall: IEC 60068-2-32
Environmental Compliance:
- RoHS-compliant materials
- CE-marked for European markets
Network Standards:
- IEEE 802.3 10/100BaseT(X) Ethernet
- Modbus/TCP protocol compliance
### 9. Additional Information
Warranty:
- Standard Warranty: 5 years (E1260 and E1260-T models)
- Relay-based models (E1214 only): 2 years due to relay lifetime limitations
Support & Maintenance:
- Firmware updates available via web console or ioSearch utility.
- Configuration import/export for easy replication across multiple units.
- Technical support available through Moxa’s global support network:
- Americas: +1-888-669-2872
- Europe: +49-89-3700399-0
- Asia-Pacific: +886-2-8919-1230
- China: +86-21-5258-9955
- Online Support: [www.moxa.com/support](https://www.moxa.com/support)
Maintenance Recommendations:
- Periodically verify sensor calibration using the built-in RTD calibration function (30 seconds per channel).
- Inspect wiring and grounding connections for mechanical stress or corrosion.
- Keep firmware updated to ensure compatibility with the latest SCADA and OPC standards.
Software Ecosystem:
- Active OPC Server Lite: Free push-based OPC DA 3.0 server for SCADA integration.
- MXIO Library: API for Windows and Linux for custom application development.
- ioSearch Utility: Device discovery, IP configuration, and firmware management.
Firmware & Configuration Management:
- Web-based firmware upgrade capability.
- Import/export configuration files for backup or deployment.
- Peer-to-peer and safe-mode configuration for fail-safe operation.
### Summary
The Moxa ioLogik E1260 is a compact, high-precision Ethernet remote I/O module optimized for temperature monitoring using RTD sensors. It combines industrial reliability, flexible networking, and intelligent communication features to simplify distributed data acquisition in automation environments. With its dual Ethernet ports, 16-bit resolution, and support for Moxa’s Active OPC Server Lite, the E1260 delivers efficient, scalable, and low-latency integration into SCADA and control systems. Its rugged design, wide temperature tolerance, and long MTBF make it ideal for harsh industrial and infrastructure applications requiring dependable, real-time temperature data over Ethernet networks.
-
ioLogik_E1200.pdf
PDF Catalog
No accessories available.