LOOKING FOR THE RIGHT

INDUSTRIAL SOLUTION?

Discover embedded, communication and automation solutions tailored to your application.

EX9044D-M

4DI (isolated), 8 DO (open collector),LED, Modbus
135,00 EUR

including VAT 160.65 EUR

  • Manufacturer TOPSCCC
  • Category: Modules Digital IO
  • The ExpertDAQ EX9044D‑M is a rugged, industrial‑grade digital input/output (DIO) module designed for distributed control and monitoring applications. It provides 4 isolated digital inputs and 8 open‑collector digital outputs, communicating via an RS‑485 interface using the Modbus RTU protocol. The module is engineered for high reliability, wide temperature operation, and flexible integration into automation systems, SCADA networks, and remote I/O architectures.
- 4 Isolated Digital Inputs: Each input channel is optically isolated to 3750 Vrms, ensuring protection against electrical noise and ground loops.
- 8 Open‑Collector Digital Outputs: NPN transistor outputs capable of sinking up to 375 mA per channel at voltages up to 30 V DC.
- RS‑485 Communication: Two‑wire half‑duplex interface supporting baud rates from 1200 bps to 115.2 kbps.
- Modbus RTU Protocol: Fully compliant with Modbus RTU for easy integration with PLCs, HMIs, and SCADA systems.
- LED Channel Indicators: 12 status LEDs (4 for inputs, 8 for outputs) provide real‑time visual feedback of channel states.
- Dual Watchdog System: Hardware and software watchdogs ensure continuous operation and fail‑safe output control.
- Wide Power Supply Range: Operates from +10 V DC to +30 V DC, with low power consumption (approx. 1.7 W).
- Extended Temperature Range: Designed for harsh environments, operating from −25 °C to +75 °C.
- EEPROM Configuration Storage: Retains address, baud rate, and protocol settings even after power loss.
- INIT* Mode: Hardware switch or pin allows reset to default configuration for recovery or reconfiguration.
- Manual or Software Configuration: Parameters can be set via serial commands or configuration software.
- Compact and Robust Design: Suitable for DIN‑rail or panel mounting in industrial control cabinets.

Country of origin: Taiwan R.O.C.

Customs tariff number: 8517 6200 900

Comprehensive Product Summary – ExpertDAQ EX9044D‑M Digital I/O Module




### 1. Product Overview

Product Name: ExpertDAQ EX9044D‑M
Model: EX9044D‑M
Series: EX9000 Series Digital I/O Modules
Article Number: EX9044D‑M
Manufacturer: ExpertDAQ (Expert Data Acquisition Systems)

The ExpertDAQ EX9044D‑M is a rugged, industrial‑grade digital input/output (DIO) module designed for distributed control and monitoring applications. It provides 4 isolated digital inputs and 8 open‑collector digital outputs, communicating via an RS‑485 interface using the Modbus RTU protocol. The module is engineered for high reliability, wide temperature operation, and flexible integration into automation systems, SCADA networks, and remote I/O architectures.




### 2. Key Features

- 4 Isolated Digital Inputs: Each input channel is optically isolated to 3750 Vrms, ensuring protection against electrical noise and ground loops.
- 8 Open‑Collector Digital Outputs: NPN transistor outputs capable of sinking up to 375 mA per channel at voltages up to 30 V DC.
- RS‑485 Communication: Two‑wire half‑duplex interface supporting baud rates from 1200 bps to 115.2 kbps.
- Modbus RTU Protocol: Fully compliant with Modbus RTU for easy integration with PLCs, HMIs, and SCADA systems.
- LED Channel Indicators: 12 status LEDs (4 for inputs, 8 for outputs) provide real‑time visual feedback of channel states.
- Dual Watchdog System: Hardware and software watchdogs ensure continuous operation and fail‑safe output control.
- Wide Power Supply Range: Operates from +10 V DC to +30 V DC, with low power consumption (approx. 1.7 W).
- Extended Temperature Range: Designed for harsh environments, operating from −25 °C to +75 °C.
- EEPROM Configuration Storage: Retains address, baud rate, and protocol settings even after power loss.
- INIT* Mode: Hardware switch or pin allows reset to default configuration for recovery or reconfiguration.
- Manual or Software Configuration: Parameters can be set via serial commands or configuration software.
- Compact and Robust Design: Suitable for DIN‑rail or panel mounting in industrial control cabinets.




### 3. Technical Specifications

| Parameter | Specification |
|----------------|-------------------|
| Digital Inputs | 4 isolated channels with common source |
| Input Type | Dry contact or TTL/CMOS compatible |
| Input Impedance | 3 kΩ |
| Logic Level 0 | ≤ +1 V DC |
| Logic Level 1 | +4 V DC – +30 V DC |
| Isolation Voltage (Input) | 3750 Vrms (photo‑isolation) |
| Digital Outputs | 8 isolated open‑collector (NPN) channels with common power |
| Max Load Voltage | +30 V DC |
| Max Sink Current | 375 mA per channel |
| Isolation Voltage (Output) | 3000 V DC |
| Interface | RS‑485, 2‑wire, half‑duplex |
| Supported Baud Rates | 1200, 2400, 4800, 9600, 19.2 k, 38.4 k, 57.6 k, 115.2 k bps |
| Protocol | Modbus RTU |
| Power Supply | +10 V DC – +30 V DC |
| Power Consumption | 1.5 W – 1.7 W typical |
| Operating Temperature | −25 °C – +75 °C |
| Storage Temperature | −30 °C – +75 °C |
| Isolation Protection | 3000 V DC between I/O and logic |
| LED Indicators | 12 (4 × DI, 8 × DO) |
| Mounting | DIN‑rail or panel mount |
| Communication Distance | Up to 1200 m without repeater |
| Maximum Modules per RS‑485 Network | 256 modules |
| Housing Material | Industrial‑grade ABS or metal enclosure (depending on configuration) |
| Approximate Weight | ~150 g (typical for EX9000 series modules) |




### 4. Functionality

The EX9044D‑M functions as a remote digital I/O expansion device in distributed control systems. It connects to a host controller, PLC, or PC via an RS‑485 network and exchanges data using Modbus RTU commands.

Operation Principle:
- Inputs: The four isolated digital inputs detect external logic levels or contact closures. Each input is optically isolated to protect against voltage surges and noise.
- Outputs: The eight open‑collector outputs act as low‑side switches, capable of driving relays, lamps, solenoids, or other DC loads up to 30 V DC.
- Communication: The module transmits and receives Modbus RTU frames, allowing read/write access to input/output states, counters, and configuration registers.
- Watchdog Control: The dual watchdog system monitors both module operation and host communication. If a fault or timeout occurs, outputs revert to predefined safe states.
- EEPROM Configuration: Stores address, baud rate, and protocol mode (Normal or Modbus RTU).
- INIT* Mode: Allows resetting to default parameters (Address = 01, Baud = 9600 bps, Modbus RTU enabled).

Typical Applications:
- Industrial automation and process control
- Building management systems (BMS)
- Remote monitoring and telemetry
- Machine control and safety interlocks
- Energy management and environmental monitoring
- SCADA and DCS I/O expansion

Compatibility:
- Compatible with Modbus RTU master devices such as PLCs, HMIs, and SCADA software.
- Integrates with ExpertDAQ configuration tools and third‑party Modbus utilities.




### 5. Components & Accessories

Included Components:
- EX9044D‑M module
- Terminal block connectors for power and I/O wiring
- Quick start guide or user manual
- Configuration software (downloadable or supplied)

Optional Accessories:
- RS‑485 to USB or RS‑232 converters
- RS‑485 repeaters for extended distance (> 1200 m)
- DIN‑rail mounting brackets
- Power supply units (10–30 V DC regulated)
- Shielded twisted‑pair communication cables

Connectors:
- Power Input: 2‑pin terminal block (+V DC, GND)
- RS‑485 Interface: 2‑pin terminal block (DATA+, DATA−)
- Digital Inputs: 4‑channel terminal block (DI0–DI3, COM)
- Digital Outputs: 8‑channel terminal block (DO0–DO7, COM)




### 6. Installation & Setup

Requirements:
- DC power supply (10–30 V DC, ≥ 1.7 W capacity)
- RS‑485 network connection (twisted‑pair cable, 120 Ω termination recommended)
- Host controller or PC with Modbus RTU master capability

Mounting Options:
- DIN‑rail mounting in control cabinets
- Panel mounting using screws or brackets

Configuration Steps:
1. Power Connection: Connect +V DC and GND to the power terminals.
2. RS‑485 Wiring: Connect DATA+ and DATA− to the network bus. Observe polarity.
3. I/O Wiring: Connect input sensors or switches to DI0–DI3 and output loads to DO0–DO7.
4. Default Settings:
- Address = 01
- Baud Rate = 9600 bps
- Protocol = Modbus RTU
5. INIT* Mode (if needed):
- Power off the module.
- Short INIT* pin to GND or slide INIT switch to “Init” position.
- Power on to enter INIT* mode (Address = 00, Baud = 9600 bps).
6. Software Configuration: Use Modbus commands or ExpertDAQ software to set address, baud rate, and data format.
7. Verification: Check LED indicators for power and channel status.

Network Integration:
- Up to 256 modules can share one RS‑485 bus.
- Maximum cable length: 1200 m without repeater.
- Use termination resistors and biasing resistors for stable communication.




### 7. Performance & Capabilities

Speed and Communication:
- Baud rates selectable from 1200 bps to 115.2 kbps.
- Supports Modbus RTU function codes 0x01, 0x02, 0x03, 0x04, 0x05, 0x0F, and others for reading/writing I/O and configuration registers.
- Response time typically within milliseconds depending on baud rate and network load.

Capacity:
- 4 digital input channels with counter and latch functions.
- 8 digital output channels with configurable safe and power‑on values.
- Each input channel can record pulse counts up to 65,535 (16‑bit counter).

Efficiency and Reliability:
- Low power consumption (1.7 W typical).
- Dual watchdog (hardware + host) ensures continuous operation.
- EEPROM retains configuration during power loss.
- LED indicators simplify diagnostics and maintenance.

Limitations:
- Outputs are open‑collector type (NPN) and require external pull‑up or load connection.
- No analog input/output capability.
- RS‑485 communication only (no Ethernet or USB onboard).




### 8. Standards & Compliance

Communication Standards:
- RS‑485 (EIA/TIA‑485) compliant
- Modbus RTU protocol compliant

Electrical & Safety:
- Isolation voltage: 3000 V DC between I/O and logic
- Input photo‑isolation: 3750 Vrms
- Designed for industrial EMC environments

Environmental:
- Operating temperature: −25 °C – +75 °C
- Storage temperature: −30 °C – +75 °C
- Suitable for industrial and outdoor enclosures (with appropriate housing)

Regulatory Compliance (typical for ExpertDAQ modules):
- CE (EMC and Low Voltage Directive)
- RoHS compliant
- FCC Class A (industrial environment)




### 9. Additional Information

Warranty:
Typically covered by a 2‑year limited manufacturer’s warranty against defects in materials and workmanship (refer to ExpertDAQ warranty policy).

Technical Support:
ExpertDAQ provides technical documentation, configuration utilities, and firmware updates via its website. Support is available through email and authorized distributors.

Maintenance:
- Periodically inspect wiring and terminal connections.
- Ensure adequate ventilation and avoid exposure to moisture or corrosive environments.
- Firmware updates can be applied via RS‑485 interface when available.

Firmware & Updates:
- Firmware version can be read using command `$AAF`.
- Module name and configuration can be read or set using `$AAM` and `~AAO(Data)` commands.
- Supports Modbus mapping for all I/O, watchdog, and configuration registers.

Modbus Register Mapping (Summary):
| Function | Register Range | Access | Description |
|---------------|--------------------|-------------|-----------------|
| DO Channels | 00001–00008 | R/W | Digital output states |
| DI Channels | 10001–10004 | R | Digital input states |
| DI Latch High/Low | 00065–00100 | R | Latched input states |
| DI Counters | 30001–30004 | R | Input pulse counters |
| Clear DI Counters | 00513–00516 | W | Reset counters |
| DO Safe Values | 00129–00136 | R/W | Output safe states |
| DO Power‑On Values | 00161–00168 | R/W | Output startup states |
| Watchdog Timeout | 40489 | R/W | Timeout value (0–255 × 0.1 s) |
| Watchdog Enable | 00261 | R/W | Enable/disable WDT |
| WDT Status | 00270 | R/W | Timeout status (clearable) |
| Module Name | 40483–40484 | R | ASCII code of module name |
| Module Address | 40485 | R/W | RS‑485 address (1–247) |
| Baud Rate | 40486 | R/W | Communication speed |

Watchdog Operation:
- Module Watchdog: Hardware circuit resets module if internal fault occurs.
- Host Watchdog: Software timer monitors communication; if timeout occurs, outputs revert to safe values.
- Timeout adjustable from 0.1 s to 25.5 s (0x01–0xFF).

Power‑On and Safe Values:
- Configurable via Modbus or ASCII commands (`~AA4V`, `~AA5V`).
- Define output states after power‑up or communication loss.

Firmware Commands (ASCII Mode):
- `$AA6` – Read digital I/O status
- `@AA(Data)` – Set digital outputs
- `$AAF` – Read firmware version
- `$AAM` – Read module name
- `$AAP` / `$AAPN` – Read/set protocol mode (Normal or Modbus RTU)
- `~AA3EVV` – Set host watchdog timeout value
- `~AA4V` / `~AA5V` – Read/set power‑on and safe values

Default Configuration:
- Address: 01
- Baud Rate: 9600 bps
- Protocol: Modbus RTU
- Data Format: 8 N 1 (no parity, 1 stop bit)

Recovery Procedure (INIT* Mode):
1. Power off the module.
2. Connect INIT* pin to GND or slide INIT switch to “Init”.
3. Power on; module enters INIT* mode (Address = 00, Baud = 9600 bps).
4. Reconfigure address and baud rate using `%AANNTTCCFF` command.
5. Power cycle to apply new settings.




### Summary

The ExpertDAQ EX9044D‑M is a versatile and reliable RS‑485 Modbus RTU digital I/O module offering 4 isolated digital inputs and 8 open‑collector outputs. It is engineered for industrial automation environments requiring robust communication, electrical isolation, and flexible configuration. With its dual watchdog system, wide operating temperature range, and comprehensive Modbus register mapping, the EX9044D‑M provides a dependable solution for remote monitoring, control, and data acquisition tasks.

Its combination of high isolation, low power consumption, and ease of integration makes it suitable for a wide range of applications—from factory automation and process control to building management and energy systems—where reliability and communication integrity are critical.

No accessories available.