EX9050AHD-M

8 DI(Sink), 8 DO(Open collector:PNP),LED, Modbus w WDT
148,00 EUR

including VAT 176.12 EUR

  • Manufacturer TOPSCCC
  • Category: Modules Digital IO
  • The EX9050AHD-M is a high-performance, non-isolated digital input/output (DIO) module designed for industrial automation, remote monitoring, and control applications. It belongs to the ExpertDAQ EX9000 series and communicates via the RS-485 interface using the Modbus RTU protocol. The module provides 8 digital input (sink) channels and 8 digital output (source, open-collector PNP) channels, making it suitable for a wide range of digital control and signal acquisition tasks.
- 8 Digital Inputs (Sink Type): Accepts input voltages from +4V to +30VDC with a logic low threshold below +1VDC.
- 8 Digital Outputs (Source Type, PNP): Open-collector transistor outputs capable of sourcing up to 30–50mA per channel at +10V to +30VDC.
- RS-485 Communication Interface: Two-wire half-duplex communication supporting baud rates from 1200 to 115200 bps.
- Modbus RTU Protocol Support: Fully compatible with Modbus RTU for easy integration into industrial networks.
- Dual Watchdog System: Includes both hardware (module) and software (host) watchdogs for enhanced reliability and fault recovery.
- LED Indicators: 16 LEDs provide real-time status for each input and output channel.
- Wide Power Supply Range: Operates from +10VDC to +30VDC with low power consumption (1.9W typical).
- Extended Temperature Range: Designed for industrial environments with operating temperatures from -25°C to +75°C.
- EEPROM Configuration Storage: Retains configuration parameters such as address, baud rate, and protocol settings.
- INIT* Mode for Configuration Recovery: Allows resetting or reconfiguring the module if communication parameters are lost.
- Compact and Robust Design: Built for DIN-rail or panel mounting in industrial control cabinets.
- Supports up to 256 Modules per RS-485 Network: Scalable architecture for large distributed I/O systems.
- Optional RS-485 Repeaters: Extend communication distance by up to 1200 meters per segment.

Country of origin: Taiwan R.O.C.

Customs tariff number: 8517 6200 900

Comprehensive Product Summary – ExpertDAQ EX9050AHD-M Digital I/O Module




### 1. Product Overview

Product Name: ExpertDAQ EX9050AHD-M
Model Number: EX9050AHD-M
Series: EX9000 Series Digital I/O Modules
Article Number: EX9050AHD-M
Manufacturer: ExpertDAQ (Expert Data Acquisition Systems)

The EX9050AHD-M is a high-performance, non-isolated digital input/output (DIO) module designed for industrial automation, remote monitoring, and control applications. It belongs to the ExpertDAQ EX9000 series and communicates via the RS-485 interface using the Modbus RTU protocol. The module provides 8 digital input (sink) channels and 8 digital output (source, open-collector PNP) channels, making it suitable for a wide range of digital control and signal acquisition tasks. It features dual watchdog protection (hardware and software), LED status indicators, and a wide operating temperature range for reliable operation in harsh environments.




### 2. Key Features

- 8 Digital Inputs (Sink Type): Accepts input voltages from +4V to +30VDC with a logic low threshold below +1VDC.
- 8 Digital Outputs (Source Type, PNP): Open-collector transistor outputs capable of sourcing up to 30–50mA per channel at +10V to +30VDC.
- RS-485 Communication Interface: Two-wire half-duplex communication supporting baud rates from 1200 to 115200 bps.
- Modbus RTU Protocol Support: Fully compatible with Modbus RTU for easy integration into industrial networks.
- Dual Watchdog System: Includes both hardware (module) and software (host) watchdogs for enhanced reliability and fault recovery.
- LED Indicators: 16 LEDs provide real-time status for each input and output channel.
- Wide Power Supply Range: Operates from +10VDC to +30VDC with low power consumption (1.9W typical).
- Extended Temperature Range: Designed for industrial environments with operating temperatures from -25°C to +75°C.
- EEPROM Configuration Storage: Retains configuration parameters such as address, baud rate, and protocol settings.
- INIT* Mode for Configuration Recovery: Allows resetting or reconfiguring the module if communication parameters are lost.
- Compact and Robust Design: Built for DIN-rail or panel mounting in industrial control cabinets.
- Supports up to 256 Modules per RS-485 Network: Scalable architecture for large distributed I/O systems.
- Optional RS-485 Repeaters: Extend communication distance by up to 1200 meters per segment.




### 3. Technical Specifications

Interface: RS-485, 2-wire half-duplex
Communication Speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Protocol: Modbus RTU (default), ASCII command mode available via INIT* mode

Digital Inputs (Sink Type):
- Channels: 8 non-isolated
- Logic Level 0: +1VDC max
- Logic Level 1: +4VDC to +30VDC
- Input Impedance: 3 kΩ
- Common Ground: Shared with outputs

Digital Outputs (Source Type, PNP):
- Channels: 8 non-isolated
- Output Type: Open-collector transistor (PNP)
- Load Voltage: +10VDC to +30VDC
- Max Load Current: 30–50mA per channel
- Short-Circuit Protection: Yes
- Recommended Load: Resistive or inductive (with flyback diode protection)

Power Supply:
- Input Voltage: +10VDC to +30VDC
- Power Consumption: 1.9W typical

Environmental Conditions:
- Operating Temperature: -25°C to +75°C
- Storage Temperature: -30°C to +75°C
- Humidity: 10–90% RH, non-condensing

Indicators:
- 16 LEDs (8 for inputs, 8 for outputs)

Physical Characteristics:
- Mounting: DIN-rail or panel mount
- Enclosure: Industrial-grade plastic housing
- Dimensions and Weight: (Manufacturer standard EX9000 form factor; typically compact, lightweight for control panels)




### 4. Functionality

The EX9050AHD-M functions as a remote digital I/O expansion module for Modbus RTU networks. It converts digital input and output signals into Modbus-compatible data accessible by PLCs, SCADA systems, or industrial PCs.

Operation Principle:
- Inputs: The 8 sink-type digital inputs detect external voltage signals (4–30VDC) and translate them into logic states readable via Modbus commands.
- Outputs: The 8 PNP open-collector outputs source current to external loads such as relays, solenoids, or indicator lamps.
- Communication: The module exchanges data over RS-485 using Modbus RTU commands, supporting both single and multi-channel read/write operations.
- Watchdog Functions:
- *Module Watchdog* monitors internal operation and resets the module if a fault occurs.
- *Host Watchdog* monitors communication with the master; if a timeout occurs, outputs revert to predefined safe values.
- EEPROM Configuration: Stores address, baud rate, and protocol settings to retain configuration after power cycles.
- INIT* Mode: Enables recovery or reconfiguration by setting the module to default communication parameters (Address=00, Baud=9600bps).

Applications:
- Industrial automation and process control
- Remote digital signal acquisition
- Machine monitoring and control
- Building automation systems
- Energy management and environmental monitoring
- Integration with PLCs, HMIs, and SCADA systems

Compatibility:
- Compatible with Modbus RTU master devices (PLCs, HMIs, SCADA software).
- Supports ASCII command mode for configuration and diagnostics.
- Can be integrated with other ExpertDAQ EX9000 modules in a single RS-485 network.




### 5. Components & Accessories

Included Components:
- EX9050AHD-M module
- User manual and configuration guide
- Mounting hardware (DIN-rail clip or panel bracket)
- Configuration utility software (for Windows)

Optional Accessories:
- RS-485 repeaters (to extend communication distance)
- RS-485 to USB converters for PC configuration
- Power supply units (10–30VDC regulated)
- Terminal blocks and wiring harnesses
- Protective diodes for inductive load suppression

Connectors:
- RS-485 communication terminals (A/B differential pair)
- Power input terminals (+V, GND)
- Digital input/output terminal blocks (DI0–DI7, DO0–DO7, GND common)




### 6. Installation & Setup

Requirements:
- DC power supply (10–30VDC, 1.9W minimum)
- RS-485 network connection (twisted pair cable, 120Ω termination recommended)
- Modbus RTU master device or configuration PC

Mounting Options:
- DIN-rail mounting (standard industrial control panel installation)
- Panel mounting (optional brackets)

Configuration Steps:
1. Power Connection: Connect +V and GND to a regulated DC power source.
2. RS-485 Wiring: Connect A/B lines to the RS-485 network. Observe polarity.
3. Address and Baud Rate Setup:
- Default: Address = 01, Baud = 9600 bps, Protocol = Modbus RTU.
- Use INIT* mode to reset or reconfigure if communication is lost.
4. INIT* Mode Activation:
- Power off the module.
- Slide the INIT* switch (rear side) to the “Init” position or short INIT* to GND.
- Power on to enter configuration mode.
- Send ASCII commands to set new address, baud rate, or checksum.
- Return switch to “Normal” position and power cycle to apply settings.
5. Network Integration: Connect up to 256 modules per RS-485 segment; use repeaters for longer distances (up to 1200m per segment).
6. Verification: Use LED indicators or Modbus read commands to verify input/output operation.




### 7. Performance & Capabilities

Speed and Communication:
- Baud rates selectable from 1200 to 115200 bps.
- Supports Modbus RTU function codes for reading/writing coils, registers, and counters.
- Response time optimized for real-time control applications.

Capacity:
- 8 digital inputs and 8 digital outputs per module.
- Up to 256 modules per RS-485 network (2048 inputs and 2048 outputs total).

Efficiency:
- Low power consumption (1.9W).
- Reliable operation in extended temperature environments.
- Dual watchdog ensures continuous operation and system safety.

Limitations:
- Non-isolated channels (common ground shared between inputs and outputs).
- Output current limited to 30–50mA per channel; external relays recommended for higher loads.
- Requires external diode protection for inductive loads.




### 8. Standards & Compliance

Communication Standards:
- RS-485 (EIA/TIA-485)
- Modbus RTU protocol compliance

Electrical & Safety:
- CE compliant (EMC and low-voltage directives)
- RoHS compliant (lead-free manufacturing)

Environmental Standards:
- Designed for industrial temperature range (-25°C to +75°C)
- Suitable for harsh industrial environments with vibration and electrical noise immunity

Quality Assurance:
- Factory-tested for communication integrity and I/O accuracy
- EEPROM-based configuration retention ensures data reliability




### 9. Additional Information

Warranty:
- Standard manufacturer warranty (typically 2 years, depending on region and distributor).

Technical Support:
- ExpertDAQ provides technical documentation, configuration utilities, and firmware updates.
- Support available via email, online resources, and authorized distributors.

Maintenance:
- Periodic inspection of wiring and terminal connections recommended.
- Ensure proper grounding and shielding for RS-485 networks.
- Firmware updates available for performance enhancements and bug fixes.

Firmware & Updates:
- Firmware version readable via Modbus command `$AAF`.
- Module name and configuration retrievable via `$AAM` and `$AA2` commands.
- Supports firmware upgrades through ExpertDAQ utilities.

Reliability Features:
- Dual watchdog (hardware + host) ensures system stability.
- Safe Value and Power-On Value configurations protect controlled devices during resets or communication failures.
- EEPROM stores user-defined safe and power-on states for each output channel.

Example Modbus Mapping:
- DO channels: Coils 00001–00008 (read/write)
- DI channels: Discrete inputs 10001–10008 (read-only)
- DI counters: Input registers 30001–30008
- WDT configuration: Holding registers 40489 (timeout value), 00261 (enable/disable)
- Module name and address stored in holding registers 40483–40486

Host Watchdog Operation:
- Timeout interval configurable from 0.1 to 25.5 seconds (01h–FFh).
- If timeout occurs, outputs revert to Safe Value.
- Host can reset watchdog via `~` or `~AA1` commands.

Power-On and Safe Values:
- Configurable via `~AA5V` commands.
- Ensures predictable output states after power-up or communication loss.




###
Summary

The
ExpertDAQ EX9050AHD-M is a robust, flexible, and efficient digital I/O module engineered for industrial automation and remote control systems. With 8 sink-type digital inputs and 8 source-type (PNP) digital outputs, it provides reliable signal interfacing for sensors, switches, and actuators. Its RS-485 Modbus RTU communication ensures seamless integration with PLCs, SCADA systems, and other Modbus-compatible devices. The inclusion of dual watchdog protection, EEPROM configuration storage, and wide environmental tolerance** makes it ideal for mission-critical applications requiring high reliability and minimal downtime.

Whether used in factory automation, building management, or process control, the EX9050AHD-M delivers dependable performance, easy configuration, and long-term operational stability in demanding industrial environments.