LOOKING FOR THE RIGHT

INDUSTRIAL SOLUTION?

Discover embedded, communication and automation solutions tailored to your application.

HSL-DI64-P-DIN

Economic HSL 64chan PNP in
  • Manufacturer Adlink Technology Inc.
  • Category: HSL RT IO System
  • The HSL-DI64-P-DIN is an economic, high-performance discrete input daughter board designed for use within ADLINK’s HSL (High Speed Link) industrial automation system. It provides 64 channels of PNP sourcing inputs, optimized for high-speed, reliable digital signal acquisition in distributed control and monitoring applications. The module integrates seamlessly with HSL terminal bases such as HSL-TB32-U-DIN and HSL-TB64-DIN, offering flexible installation and expansion options for industrial environments.
- 64-Channel PNP Sourcing Input: Supports 64 discrete input channels for wet contact or PNP-type signal sources.
- High-Speed Link (HSL) Interface: Designed for ADLINK’s HSL system, enabling fast, deterministic communication between distributed I/O modules and controllers.
- DIN-Rail Mountable Design: Compatible with DIN socket terminal bases for easy installation in control cabinets.
- Compact and Modular Architecture: The daughter board can be combined with terminal bases to form compact I/O nodes.
- LED Status Indicators:
- Power (Red): Indicates active DC power.
- Link (Green): Displays communication link status.
- Input (Green): Shows individual channel activity.
- Flexible Power Input: Operates from a wide +10 VDC to +30 VDC external power supply.
- Low Power Consumption: Typical consumption of 1.8 W, ensuring energy efficiency.
- Fast Response Time: Input response time of 2 ms (ON/OFF) for high-speed digital signal processing.
- High Input Impedance: 4.7 kΩ input impedance ensures minimal loading on connected sensors.
- Industrial-Grade Reliability: Designed for robust operation in industrial automation environments.
- Address Configuration via DIP Switch: Supports flexible address allocation for multi-module systems.
- Compatibility with HSL Terminal Bases: Works with both HSL-TB32-U-DIN and HSL-TB64-DIN terminal bases for 32- or 64-channel configurations.

Country of origin: Taiwan R.O.C.

Customs tariff number: 8473 3020 000

Comprehensive Product Summary: HSL-DI64-P-DIN




### 1. Product Overview

Product Name: HSL-DI64-P-DIN
Model Number: HSL-DI64-P-DIN
Series: HSL (High Speed Link for Industry Automation Solutions)
Article Number: HSL-DI64-P-DIN
Manufacturer: ADLINK Technology Inc.
Product Type: Economic HSL 64-channel PNP sourcing input daughter board
Product Category: Industrial Automation I/O Module – Discrete Input Board

The HSL-DI64-P-DIN is an economic, high-performance discrete input daughter board designed for use within ADLINK’s HSL (High Speed Link) industrial automation system. It provides 64 channels of PNP sourcing inputs, optimized for high-speed, reliable digital signal acquisition in distributed control and monitoring applications. The module integrates seamlessly with HSL terminal bases such as HSL-TB32-U-DIN and HSL-TB64-DIN, offering flexible installation and expansion options for industrial environments.




### 2. Key Features

- 64-Channel PNP Sourcing Input: Supports 64 discrete input channels for wet contact or PNP-type signal sources.
- High-Speed Link (HSL) Interface: Designed for ADLINK’s HSL system, enabling fast, deterministic communication between distributed I/O modules and controllers.
- DIN-Rail Mountable Design: Compatible with DIN socket terminal bases for easy installation in control cabinets.
- Compact and Modular Architecture: The daughter board can be combined with terminal bases to form compact I/O nodes.
- LED Status Indicators:
- Power (Red): Indicates active DC power.
- Link (Green): Displays communication link status.
- Input (Green): Shows individual channel activity.
- Flexible Power Input: Operates from a wide +10 VDC to +30 VDC external power supply.
- Low Power Consumption: Typical consumption of 1.8 W, ensuring energy efficiency.
- Fast Response Time: Input response time of 2 ms (ON/OFF) for high-speed digital signal processing.
- High Input Impedance: 4.7 kΩ input impedance ensures minimal loading on connected sensors.
- Industrial-Grade Reliability: Designed for robust operation in industrial automation environments.
- Address Configuration via DIP Switch: Supports flexible address allocation for multi-module systems.
- Compatibility with HSL Terminal Bases: Works with both HSL-TB32-U-DIN and HSL-TB64-DIN terminal bases for 32- or 64-channel configurations.




### 3. Technical Specifications

Electrical Characteristics:

| Parameter | Specification |
|------------|----------------|
| Input Type | PNP Sourcing (Wet Contact) |
| Number of Channels | 64 |
| Input Current (max.) | +10 mA |
| Input Impedance | 4.7 kΩ |
| ON Voltage (min.) | 14.4 VDC |
| OFF Voltage (max.) | 5.0 VDC |
| ON Response Time | 2 ms (max.) |
| OFF Response Time | 2 ms (max.) |
| External Power Supply | +10 VDC to +30 VDC |
| Power Consumption | 1.8 W |
| Isolation | Channel-to-channel isolation via internal circuitry |
| LED Indicators | Power (Red), Link (Green), Input (Green) |

Mechanical Dimensions:

| Configuration | Dimensions (mm) |
|----------------|----------------|
| Daughter Board Only | 100 × 78.2 |
| With HSL-TB32-U-DIN | 126 × 120.1 × 107.3 |
| With HSL-TB64-DIN | 168.7 × 120.1 × 107.3 |

Weight: 72 g (board only)
Mounting Type: DIN-rail compatible via terminal base
Material: Industrial-grade PCB with protective coating




### 4. Functionality

The HSL-DI64-P-DIN functions as a discrete input interface module within the HSL distributed I/O system. It receives digital signals from field devices such as sensors, switches, and pushbuttons, converting them into logic-level signals for transmission over the HSL network to a host controller or PLC.

Operating Principle:
- Each input channel detects the presence of a voltage signal from a PNP-type sensor or wet contact device.
- The board sources current to the input device, registering a logic “1” when the input voltage exceeds the ON threshold (≥14.4 VDC) and a logic “0” when below the OFF threshold (≤5.0 VDC).
- The onboard microcontroller communicates input states to the HSL master via RS-422 differential signaling, ensuring noise immunity and high-speed data transfer.

Use Cases and Applications:
- Industrial automation and process control systems
- Machine control panels and distributed I/O networks
- Factory monitoring and data acquisition systems
- Integration with PLCs, motion controllers, and SCADA systems
- Applications requiring high-density digital input acquisition

Compatibility:
- Fully compatible with ADLINK’s HSL system architecture
- Works with HSL-TB32-U-DIN (32-channel terminal base) and HSL-TB64-DIN (64-channel terminal base)
- Supports both slot I and slot II configurations on the HSL-TB64-DIN for channel mapping from 0–63




### 5. Components & Accessories

Included Components:
- HSL-DI64-P-DIN daughter board
- LED indicators for power, link, and input status
- DIP switch for address configuration
- RS-422 communication interface (RX+, RX–, TX+, TX–)

Optional Accessories:
- HSL-TB32-U-DIN: 32-channel I/O terminal base with DIN socket
- HSL-TB64-DIN: 64-channel I/O terminal base with DIN socket
- Cabling and Connectors: Standard HSL communication cables and power connectors

Connector Pin Assignments (JP3/JP4):
- Power and Communication:
- Pin 1: +VS (+10V~+30V DC)
- Pin 2: GND
- Pin 5: RX+ (RS-422 receive positive)
- Pin 7: RX– (RS-422 receive negative)
- Pin 6: TX+ (RS-422 transmit positive)
- Pin 8: TX– (RS-422 transmit negative)
- Discrete Input Channels: DI0–DI31 (for 32-channel configuration); DI0–DI63 (for 64-channel configuration)

LED Indicators:
- Red LED: Active DC power
- Green LED (Link): Communication link established
- Green LEDs (Input): Channel-specific input status




### 6. Installation & Setup

Installation Requirements:
- External DC power supply: +10 VDC to +30 VDC
- Compatible terminal base (HSL-TB32-U-DIN or HSL-TB64-DIN)
- DIN-rail mounting capability for terminal base
- Proper grounding and shielding for industrial environments

Mounting Options:
- DIN-rail mounting via terminal base
- Panel mounting possible with appropriate brackets

Configuration:
- Address Setting: Configured via onboard DIP switch.
- The DI32 occupies two consecutive address allocations starting from an odd address.
- Switch bit 1 is fixed to ON.
- Example address mapping:
- 100000 → Address 1, 2
- 110000 → Address 3, 4
- …
- 101111 → Address 61, 62

Field I/O Wiring:
- With HSL-TB32-U-DIN: Channels 0–31 mapped to terminals 0–31.
- With HSL-TB64-DIN: Channels 0–63 mapped across Slot I and Slot II terminals (0/32 through 31/63).

Power Connection:
- Connect +VS to +10~+30 VDC supply.
- Connect GND to system ground.

Communication Connection:
- RS-422 differential lines (RX+/RX–, TX+/TX–) connect to the HSL network master or adjacent modules.




### 7. Performance & Capabilities

Speed and Responsiveness:
- Input response time: 2 ms (ON/OFF) ensures rapid detection of signal changes.
- High-speed RS-422 communication supports deterministic data transfer across the HSL network.

Capacity:
- 64 discrete input channels per module, expandable through additional HSL modules.

Efficiency:
- Low power consumption (1.8 W) minimizes heat generation and energy usage.
- High input impedance (4.7 kΩ) reduces current draw from field devices.

Reliability:
- Industrial-grade design ensures stable operation under electrical noise and vibration.
- LED diagnostics simplify troubleshooting and system monitoring.

Limitations:
- Designed for PNP (sourcing) input types only; not compatible with NPN (sinking) sensors.
- Maximum input voltage limited to 30 VDC.
- Requires HSL-compatible master controller for operation.




### 8. Standards & Compliance

Certifications and Compliance:
- Designed in accordance with industrial automation standards for discrete I/O modules.
- Complies with CE and FCC Class A industrial emissions standards (typical for ADLINK HSL products).
- Meets RoHS environmental compliance for hazardous substance reduction.
- HSL® is a registered trademark of ADLINK Technology Inc.

Industry Standards:
- RS-422 differential communication standard for noise-immune data transmission.
- DIN-rail mounting standard (EN 60715).
- Electrical safety and EMC compliance per ADLINK’s industrial product guidelines.




### 9. Additional Information

Warranty:
Standard ADLINK limited warranty (typically 1–2 years, depending on region and distributor).

Technical Support:
- Service Email: service@adlink.com.tw
- Technical Assistance: NuDAM@adlink.com.tw
- Telephone: +886-2-82265877
- Fax: +886-2-82265717

Manufacturer Website:
[http://www.adlink.com.tw](http://www.adlink.com.tw)

Maintenance:
- Periodic inspection of terminal connections and power supply recommended.
- Keep module free from dust and moisture.
- Verify LED indicators for normal operation.

Firmware and Updates:
- Firmware updates and configuration tools available through ADLINK’s HSL software suite.
- Backward compatibility maintained with existing HSL systems.

Ordering Information:
- HSL-DI64-P-DIN: 64-Channel PNP Sourcing Input Daughter Board
- HSL-TB32-U-DIN: 32-Channel I/O Terminal Base with DIN Socket (optional)
- HSL-TB64-DIN: 64-Channel I/O Terminal Base with DIN Socket (optional)

Related Models:
- HSL-DI32-DB-N: 32-Channel NPN Sinking Input Daughter Board
- HSL-DI32-DB-P: 32-Channel PNP Sourcing Input Daughter Board

Document Reference: AM-HSLDBIO002-E1.00
Copyright: © 2001 ADLINK Technology Inc.
Trademark Notice: HSL® is a registered trademark of ADLINK Technology Inc. Other product names are trademarks or registered trademarks of their respective owners.




### Summary

The ADLINK HSL-DI64-P-DIN is a cost-effective, high-density discrete input module engineered for industrial automation systems requiring reliable, high-speed digital input acquisition. With 64 PNP sourcing input channels, robust RS-422 communication, and flexible DIN-rail mounting, it provides an ideal solution for distributed I/O architectures. Its modular design, LED diagnostics, and compatibility with HSL terminal bases make it a versatile component for machine control, process monitoring, and factory automation applications. Designed under ADLINK’s High Speed Link (HSL) framework, the HSL-DI64-P-DIN delivers performance, scalability, and reliability for modern industrial environments.

No accessories available.