LOOKING FOR THE RIGHT

INDUSTRIAL SOLUTION?

Discover embedded, communication and automation solutions tailored to your application.

SVR-RMA(FIT)

Remote Access Server
1390,00 EUR

including VAT 1,654.10 EUR

  • Manufacturer Contec
  • Category: Contec System
  • The CONTEC SVR‑RMA(FIT) is an Ethernet‑based remote access server module designed for industrial automation and distributed monitoring/control networks. It is part of CONTEC’s F&eIT (Factory and Enterprise IT) Series, which integrates factory‑floor devices with enterprise‑level information systems. The SVR‑RMA(FIT) provides centralized remote access, monitoring, and control of distributed I/O devices, PLCs, and controllers through standard Ethernet infrastructure. It is engineered for DIN‑rail mounting, compactness, and reliability in industrial environments.
- Remote Monitoring and Control: Enables centralized supervision of multiple remote I/O systems via Ethernet. Supports web‑based monitoring, data logging, and alarm notification.
- Web‑based Configuration: All setup and monitoring functions are accessible through a standard web browser. No dedicated software is required for basic operation.
- Compact DIN‑Rail Design: Ultra‑compact housing (approx. 94 mm H × 64.7 mm D × 52.4 mm W) allows installation in control panels or confined spaces.
- Industrial Reliability: Fanless, diskless design with watchdog timer and wide operating temperature range (0 – 50 °C). Resistant to line noise and static discharge per IEC/EN standards.
- Ethernet Integration: 10BASE‑T/100BASE‑TX interface for seamless integration with existing LANs and Internet‑connected systems.
- Automatic Data Collection: Cyclically polls connected I/O controllers, aggregates data, and transmits it to host systems, reducing network load.
- Programless Web Monitoring: Built‑in Java applet web server allows creation of graphical monitoring screens (meters, sliders, graphs) directly in the browser.
- Scalable Architecture: Supports up to eight I/O controller units per server and up to eight servers per network segment (total 64 controllers).
- Security and Maintenance: Password‑protected access, SNMP agent support, and optional firewall integration via CONTEC Security Server modules.
- Interoperability: Compatible with CONTEC I/O Controllers (CPU‑CAxx(FIT)GY), Device Modules, and Power Supply Series.

Country of origin: Japan

Customs tariff number: 8473 3020 000

1. Product Overview

Product Name: Remote Access Server
Model: SVR‑RMA(FIT)
Series: F&eIT Series (Factory and Enterprise IT)
Article Number: SVR‑RMA(FIT)
Manufacturer: CONTEC CO., LTD., Osaka, Japan

The CONTEC SVR‑RMA(FIT) is an Ethernet‑based remote access server module designed for industrial automation and distributed monitoring/control networks. It is part of CONTEC’s F&eIT (Factory and Enterprise IT) Series, which integrates factory‑floor devices with enterprise‑level information systems. The SVR‑RMA(FIT) provides centralized remote access, monitoring, and control of distributed I/O devices, PLCs, and controllers through standard Ethernet infrastructure. It is engineered for DIN‑rail mounting, compactness, and reliability in industrial environments.




2. Key Features

- Remote Monitoring and Control: Enables centralized supervision of multiple remote I/O systems via Ethernet. Supports web‑based monitoring, data logging, and alarm notification.
- Web‑based Configuration: All setup and monitoring functions are accessible through a standard web browser. No dedicated software is required for basic operation.
- Compact DIN‑Rail Design: Ultra‑compact housing (approx. 94 mm H × 64.7 mm D × 52.4 mm W) allows installation in control panels or confined spaces.
- Industrial Reliability: Fanless, diskless design with watchdog timer and wide operating temperature range (0 – 50 °C). Resistant to line noise and static discharge per IEC/EN standards.
- Ethernet Integration: 10BASE‑T/100BASE‑TX interface for seamless integration with existing LANs and Internet‑connected systems.
- Automatic Data Collection: Cyclically polls connected I/O controllers, aggregates data, and transmits it to host systems, reducing network load.
- Programless Web Monitoring: Built‑in Java applet web server allows creation of graphical monitoring screens (meters, sliders, graphs) directly in the browser.
- Scalable Architecture: Supports up to eight I/O controller units per server and up to eight servers per network segment (total 64 controllers).
- Security and Maintenance: Password‑protected access, SNMP agent support, and optional firewall integration via CONTEC Security Server modules.
- Interoperability: Compatible with CONTEC I/O Controllers (CPU‑CAxx(FIT)GY), Device Modules, and Power Supply Series.




3. Technical Specifications

| Parameter | Specification |
|----------------|------------------|
| CPU | SH3 100 MHz (SVR‑IOA(FIT)GY) / SH4 240 MHz (SVR‑IOA2(FIT)GY) |
| Memory | Flash ROM 1 MB (8 Mbit) / 4 MB (32 Mbit); EDO DRAM 2 MB (16 Mbit) / SDRAM 32 MB (256 Mbit) |
| Interface | 10BASE‑T / 100BASE‑TX (IEEE 802.3/802.3u) |
| Power Supply | 5 V DC ± 5 % via 2‑piece detachable connector (FG terminal included) |
| Power Consumption | 0.5 A max (SVR‑IOA) / 0.7 A max (SVR‑IOA2) |
| Dimensions | 25.2 (W) × 64.7 (D) × 94.0 (H) mm (excluding protrusions) |
| Weight | Approx. 100 g |
| Mounting | 35 mm DIN rail, one‑touch installation/removal |
| Operating Temperature | 0 – 50 °C |
| Storage Temperature | –10 – 60 °C |
| Humidity | 10 – 90 % RH (non‑condensing) |
| Noise Resistance | AC line 2 kV, signal line 1 kV (IEC1000‑4‑4 Level 3 / EN61000‑4‑4 Level 3) |
| Static Resistance | Contact 4 kV, Air 8 kV (IEC1000‑4‑2 Level 2/3) |
| Vibration Resistance | 10–57 Hz 0.15 mm, 57–150 Hz 2 G (IEC68‑2‑6) |
| Impact Resistance | 15 G 11 ms half‑sine (IEC68‑2‑27) |
| Grounding | Class D (former Class 3) |
| Certifications | FCC Class A, CE (industrial use) |




4. Functionality

The SVR‑RMA(FIT) operates as a remote access and management node within a distributed F&eIT network. It automatically detects and communicates with up to eight subordinate I/O Controller Units (CPU‑CAxx(FIT)GY) sharing the same Group ID. Each controller can host up to eight Device Modules (digital, analog, counter, serial, or GPIB). The server cyclically collects I/O data, aggregates it, and provides unified access to host computers or SCADA systems.

Use Cases and Applications:
- Factory automation and process monitoring
- Remote PLC supervision and parameter updates
- Environmental and energy management systems
- Building automation and facility control
- Web‑based data acquisition and alarm notification

Compatibility:
- Fully compatible with CONTEC F&eIT Device Modules and Power Supply Series
- Supports Windows‑based host systems via API‑CAP(W32) and DDE interfaces
- Accessible from any TCP/IP‑enabled device using standard web browsers




5. Components & Accessories

Included Items:
- SVR‑RMA(FIT) main unit (SVR‑IOA(FIT)GY or SVR‑IOA2(FIT)GY)
- Power connector (2‑piece detachable)
- CD‑ROM (F&eIT Series Setup Disk with drivers, utilities, manuals)
- First Step Guide (quick start documentation)

Optional Accessories:
- Power Supplies: POW‑AD13GY, POW‑AD22GY, POW‑AD25GY (AC‑DC); POW‑DD10GY, POW‑DD43GY (DC‑DC)
- Cooling Fan: FAN‑FIT (optional, extends operating temperature to 60 °C)
- Switching Hub: SH‑8008(FIT)GY (8‑port 10/100 M auto‑switching)
- I/O Controllers: CPU‑CA10(FIT)GY, CPU‑CA20(FIT)GY
- Device Modules: Digital I/O, Analog I/O, Counter, Temperature, Serial, GPIB
- Security Server: SVR‑SEC(FIT)GY (firewall router)
- Media Converters: RP‑COM(FIT)GY, RP‑422(FIT)GY, RP‑GPIB(FIT)GY
- Wireless Access Points: FX‑DS540‑APDL/ APL (IEEE 802.11 a/b/g)




6. Installation & Setup

Mounting:
The unit mounts directly onto a standard 35 mm DIN rail using a spring‑loaded latch. Installation and removal require only a flat‑blade screwdriver. Maintain at least 2 cm clearance for ventilation, especially when using DC‑DC power supplies.

Connections:
- Power: Connect 5 V DC ± 5 % to Vo+ and Vo– terminals; FG for ground.
- Network: Connect UTP Category 5 cable to RJ‑45 port (10/100 Mbps auto‑negotiation).
- Error Output (SVR‑IOA only): Open‑collector output (30 V DC max, 10 mA min) for alarm signaling.

Configuration:
- Group ID Switch: Rotary 0–7 for operational groups; E for firmware update; F for factory reset.
- Quick Setup: Default IP address derived from MAC address (10.x.x.x).
- Custom Setup: Use F&eIT Setup Utility (API‑CAP(W32)) to assign static IP, subnet mask, and gateway.
- Web Access: Enter device IP in browser (e.g., http://192.168.x.x) to open the monitoring interface.
- Security: Set administrator and monitoring passwords via web menu.




7. Performance & Capabilities

- Processing Speed: SH4 240 MHz CPU (SVR‑IOA2) offers 2× the performance of the previous model.
- Data Polling: Cyclic collection intervals as low as 10 ms per controller; typical system refresh ≈ 20 ms for 1024 I/O points.
- Network Capacity: Up to 8 controllers per server, 8 servers per segment (64 controllers total).
- Data Throughput: 100 Mbps Ethernet full‑duplex operation.
- Web Sessions: Supports 10 simultaneous Java applets and 10 browser connections.
- Reliability: Watchdog timer monitors system health; automatic reset on fault.
- Limitations: No VPN function; requires external Security Server for advanced firewall features.




8. Standards & Compliance

- Electrical Safety: IEC 61000‑4‑4 Level 3 / EN 61000‑4‑4 Level 3 (line noise immunity)
- EMC: FCC Part 15 Class A (industrial digital device)
- Environmental: RoHS compliant; lead‑free construction
- Grounding: Class D (former Class 3) industrial ground
- Network Protocol: F&eIT Protocol (UDP/IP port 5007h) with response confirmation layer for reliable real‑time communication
- Supported Standards: IEEE 802.3/802.3u Ethernet, SNMP Agent support, DDE and SuiteLink interfaces for SCADA integration.




9. Additional Information

Warranty: One‑year limited warranty from date of purchase. Free repair or replacement for defects in materials or workmanship under normal use. Excludes damage from misuse or modification.

Support & Service:
- Technical support available via CONTEC regional offices (Japan, USA, Europe, Korea, China, Taiwan).
- Firmware updates and driver downloads available free at [www.contec.com](http://www.contec.com).
- Return Merchandise Authorization (RMA) required for service.

Maintenance:
- Periodic inspection of ventilation slots and connectors.
- Replace lithium backup battery every 6–10 years (25 °C reference).
- Firmware upgrade via Group ID “E” mode (Loader startup).

Software Support:
- API‑CAP(W32): Windows DLL library for device access (VB, VC++, Delphi, C++ Builder).
- FIT_SVR(W32): DDE/SuiteLink server for Excel and Wonderware InTouch.
- Utility Software: Node setup, firmware update, diagnostics.
- Supported OS: Windows XP/2000/NT4.0/Me/98; Linux via socket communication.

Maintenance Environment:
Operate in clean, dry locations free of corrosive gas and excessive dust. Avoid direct sunlight and vibration. Store at room temperature in original packaging when not in use.

Firmware and Protocol:
Implements CONTEC’s F&eIT Protocol over UDP/IP with response confirmation for real‑time industrial communication. Virtual address mapping provides transparent access to device resources and I/O memory spaces.




Summary

The CONTEC SVR‑RMA(FIT) Remote Access Server is a compact, industrial‑grade Ethernet module that consolidates and manages distributed I/O networks. It provides real‑time, web‑based monitoring and control without programming, supports multiple communication standards, and integrates seamlessly with CONTEC’s F&eIT ecosystem. Its robust design, flexible configuration, and open architecture make it ideal for factory automation, process control, and remote equipment management applications requiring reliability, scalability, and ease of integration.