LOOKING FOR THE RIGHT
INDUSTRIAL SOLUTION?
Discover embedded, communication and automation solutions tailored to your application.
EX9052D
8 DI (isolated, 6 differential, 2 single-ended),LED
105,00 EUR
including VAT 124.95 EUR
- 8 Isolated Digital Inputs:
Six differential and two single-ended channels with common ground, providing flexible signal interfacing for various sensor types and logic levels.
- High Isolation Protection:
3750 Vrms optical isolation between channels and system logic ensures reliable operation and protection against ground loops and electrical noise.
- Wide Input Voltage Range:
Accepts digital logic levels from +4 VDC to +30 VDC for logic high (ON) and below +1 VDC for logic low (OFF), compatible with TTL, CMOS, and open-collector signal sources.
- RS-485 Communication Interface:
Two-wire half-duplex RS-485 interface supporting up to 256 modules on a single network segment (without repeater) and cable lengths up to 1200 meters.
- Flexible Communication Protocols:
- EX9052D: ASCII command set for direct serial control.
- EX9052D-M: Modbus RTU protocol for standardized industrial communication.
- LED Channel Indicators:
Eight front-panel LEDs provide real-time visual feedback of input channel status.
- Low Power Consumption:
Typical power consumption of 1.2 W at 10–30 VDC supply voltage.
- Extended Temperature Range:
Operates reliably from -25°C to +75°C, suitable for industrial and outdoor environments.
- Dual Watchdog System:
Hardware and software watchdogs ensure continuous operation and automatic recovery from communication or system faults.
- EEPROM Configuration Storage:
Retains module address, baud rate, and configuration settings even after power loss.
- Compact and Rugged Design:
Built for DIN-rail or panel mounting, with robust housing suitable for industrial control cabinets.
Six differential and two single-ended channels with common ground, providing flexible signal interfacing for various sensor types and logic levels.
- High Isolation Protection:
3750 Vrms optical isolation between channels and system logic ensures reliable operation and protection against ground loops and electrical noise.
- Wide Input Voltage Range:
Accepts digital logic levels from +4 VDC to +30 VDC for logic high (ON) and below +1 VDC for logic low (OFF), compatible with TTL, CMOS, and open-collector signal sources.
- RS-485 Communication Interface:
Two-wire half-duplex RS-485 interface supporting up to 256 modules on a single network segment (without repeater) and cable lengths up to 1200 meters.
- Flexible Communication Protocols:
- EX9052D: ASCII command set for direct serial control.
- EX9052D-M: Modbus RTU protocol for standardized industrial communication.
- LED Channel Indicators:
Eight front-panel LEDs provide real-time visual feedback of input channel status.
- Low Power Consumption:
Typical power consumption of 1.2 W at 10–30 VDC supply voltage.
- Extended Temperature Range:
Operates reliably from -25°C to +75°C, suitable for industrial and outdoor environments.
- Dual Watchdog System:
Hardware and software watchdogs ensure continuous operation and automatic recovery from communication or system faults.
- EEPROM Configuration Storage:
Retains module address, baud rate, and configuration settings even after power loss.
- Compact and Rugged Design:
Built for DIN-rail or panel mounting, with robust housing suitable for industrial control cabinets.
Comprehensive Product Summary – ExpertDAQ EX9052D Digital Input Module
### 1. Product Overview
Product Name: ExpertDAQ EX9052D
Model: EX9052D
Series: EX9000 Series – RS-485 Digital I/O Modules
Article Number: EX9052D
Manufacturer: ExpertDAQ (Expert Data Acquisition Systems)
The ExpertDAQ EX9052D is an industrial-grade digital input module designed for distributed data acquisition and control applications over an RS-485 network. It provides eight optically isolated digital input channels, combining six differential and two single-ended inputs, and is engineered for robust performance in harsh environments. The EX9052D is part of the ExpertDAQ EX9000 modular I/O family, which supports ASCII command communication, while its variant, the EX9052D-M, supports Modbus RTU protocol for seamless integration with PLCs, SCADA systems, and industrial automation controllers.
### 2. Key Features
- 8 Isolated Digital Inputs:
Six differential and two single-ended channels with common ground, providing flexible signal interfacing for various sensor types and logic levels.
- High Isolation Protection:
3750 Vrms optical isolation between channels and system logic ensures reliable operation and protection against ground loops and electrical noise.
- Wide Input Voltage Range:
Accepts digital logic levels from +4 VDC to +30 VDC for logic high (ON) and below +1 VDC for logic low (OFF), compatible with TTL, CMOS, and open-collector signal sources.
- RS-485 Communication Interface:
Two-wire half-duplex RS-485 interface supporting up to 256 modules on a single network segment (without repeater) and cable lengths up to 1200 meters.
- Flexible Communication Protocols:
- EX9052D: ASCII command set for direct serial control.
- EX9052D-M: Modbus RTU protocol for standardized industrial communication.
- LED Channel Indicators:
Eight front-panel LEDs provide real-time visual feedback of input channel status.
- Low Power Consumption:
Typical power consumption of 1.2 W at 10–30 VDC supply voltage.
- Extended Temperature Range:
Operates reliably from -25°C to +75°C, suitable for industrial and outdoor environments.
- Dual Watchdog System:
Hardware and software watchdogs ensure continuous operation and automatic recovery from communication or system faults.
- EEPROM Configuration Storage:
Retains module address, baud rate, and configuration settings even after power loss.
- Compact and Rugged Design:
Built for DIN-rail or panel mounting, with robust housing suitable for industrial control cabinets.
### 3. Technical Specifications
| Parameter | Specification |
|----------------|-------------------|
| Model | EX9052D |
| Input Channels | 8 total (6 differential, 2 single-ended with common ground) |
| Input Type | Optically isolated digital inputs |
| Input Voltage (ON) | +4 VDC to +30 VDC |
| Input Voltage (OFF) | +1 VDC maximum |
| Input Impedance | 3 kΩ |
| Isolation Voltage | 3750 Vrms channel-to-system |
| Interface | RS-485, 2-wire half-duplex |
| Communication Speeds | 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps |
| Protocol | ASCII (EX9052D), Modbus RTU (EX9052D-M) |
| Power Supply | +10 VDC to +30 VDC |
| Power Consumption | 1.2 W typical |
| LED Indicators | 8 input status LEDs |
| Operating Temperature | -25°C to +75°C |
| Storage Temperature | -30°C to +75°C |
| Isolation Type | Optical isolation per channel |
| Configuration Memory | EEPROM (non-volatile) |
| Mounting | DIN-rail or panel mount |
| Network Capacity | Up to 256 modules per RS-485 segment |
| Maximum Cable Length | 1200 m (without repeater) |
| Housing | Industrial-grade enclosure (material not specified) |
### 4. Functionality
The EX9052D functions as a distributed digital input acquisition module within an RS-485 network. It converts discrete input signals from sensors, switches, or logic devices into serial data for transmission to a host controller or SCADA system.
Operating Principle:
- Each input channel detects a digital signal (ON/OFF) based on voltage thresholds.
- The module optically isolates each input to prevent ground potential differences and electrical interference.
- Input states are continuously monitored and can be read via ASCII commands (EX9052D) or Modbus RTU registers (EX9052D-M).
- The module supports latched input detection, allowing capture of transient pulses that might otherwise be missed during polling.
Use Cases and Applications:
- Industrial automation and process control
- Remote monitoring of digital sensors and switches
- Machine status and alarm signal acquisition
- Building automation and energy management systems
- Distributed I/O expansion for PLCs and embedded controllers
Compatibility:
- Compatible with any RS-485 master device or Modbus RTU controller.
- Works with ExpertDAQ configuration utilities and third-party SCADA software.
- Supports integration with Modbus-compatible PLCs, HMIs, and data loggers.
### 5. Components & Accessories
Included Components:
- EX9052D module unit
- Terminal block connectors for signal and power wiring
- User manual and configuration guide
- Software utility for configuration (via RS-485)
Optional Accessories:
- RS-485 to USB or RS-232 converters for PC connection
- RS-485 repeaters for extended network distances
- DIN-rail mounting clips and brackets
- Power supply units (10–30 VDC regulated)
- Shielded twisted-pair communication cables
Connectors:
- Screw-type terminal blocks for input channels and power supply
- RS-485 communication terminals (Data+, Data–, GND)
- INIT* terminal or rear-mounted switch for configuration reset
### 6. Installation & Setup
Requirements:
- DC power supply between 10 and 30 VDC
- RS-485 network connection (2-wire)
- Host controller or PC with RS-485 interface
Mounting Options:
- DIN-rail mounting in control cabinets
- Panel mounting using screws or brackets
Configuration Procedure:
1. Power Connection: Connect +V and GND to a regulated DC power source.
2. RS-485 Wiring: Connect Data+ and Data– lines to the network bus.
3. Address and Baud Rate Setup:
- Default address: 01
- Default baud rate: 9600 bps
- Configuration via ASCII command `%AANNTTCCFF` or software utility.
4. INIT* Mode:
- Activate by connecting INIT* to GND or sliding the INIT* switch to ON.
- Used for resetting configuration or changing baud rate/checksum.
5. Verification:
- Use command `$AA6` or Modbus function code 0x01 to read input status.
- Verify LED indicators correspond to input signal states.
Wiring Examples:
- Dry Contact Input: Connect switch contacts directly between input and ground.
- TTL/CMOS Input: Connect logic output to input terminal with shared ground.
- Open Collector Input: Connect transistor output to input terminal with pull-up voltage.
### 7. Performance & Capabilities
- Speed and Responsiveness:
Supports baud rates up to 115.2 kbps, allowing fast polling and data acquisition across large networks.
- Capacity:
Each module provides 8 input channels; up to 256 modules can be networked, yielding a total of 2048 digital inputs per RS-485 segment.
- Efficiency:
Low power consumption (1.2 W) minimizes heat generation and allows dense installation.
- Reliability:
Dual watchdog system ensures continuous operation:
- Module Watchdog: Hardware circuit monitors internal operation and resets the module if a fault occurs.
- Host Watchdog: Software timer monitors communication from the host; if timeout occurs, the module enters a safe state.
- Limitations:
- No digital output capability (input-only module).
- ASCII version (EX9052D) does not support Modbus RTU.
- Requires external RS-485 converter for PC connection.
### 8. Standards & Compliance
- Communication Standards:
RS-485 (EIA/TIA-485) compliant, supporting multi-drop serial communication.
- Protocol Standards:
- ASCII command set (ExpertDAQ proprietary)
- Modbus RTU (for EX9052D-M variant)
- Electrical Isolation:
3750 Vrms optical isolation per channel, meeting industrial safety and EMC requirements.
- Environmental Compliance:
Designed for industrial temperature range (-25°C to +75°C) and high electrical noise immunity.
- Regulatory Compliance:
Conforms to CE and FCC Class A industrial emissions standards (typical for ExpertDAQ modules).
### 9. Additional Information
Warranty:
Standard manufacturer warranty (typically 2 years, depending on region and distributor).
Technical Support:
ExpertDAQ provides technical documentation, configuration utilities, and firmware updates via its official website. Support includes:
- Configuration assistance
- Firmware upgrade instructions
- RS-485 network troubleshooting guides
Maintenance:
- Periodic inspection of wiring and terminal connections recommended.
- Ensure proper grounding and shielding for noise immunity.
- Firmware updates can be applied via RS-485 interface when available.
Firmware & Updates:
- Firmware version can be read using command `$AAF`.
- Example: `$01F` → `!01D04.03` indicates firmware version D04.03.
- Updates may include enhanced Modbus mapping or improved watchdog handling.
Modbus Mapping (EX9052D-M):
| Address Range | Function | Access | Description |
|--------------------|--------------|-------------|-----------------|
| 00033–00040 | Digital Input Channels DI0–DI7 | Read | Current input states |
| 00065–00072 | DI Latch High | Read | Indicates channels that have latched high |
| 00097–00104 | DI Latch Low | Read | Indicates channels that have latched low |
| 00264 | Clear Latch | Write | Clears latched input states |
| 30001–30008 | DI Counters | Read | 16-bit input pulse counters |
| 00513–00520 | Clear DI Counters | Write | Resets input counters |
Default Communication Settings:
- Address: 01
- Baud Rate: 9600 bps
- Data Format: 8N1 (8 data bits, no parity, 1 stop bit)
- Protocol: ASCII (EX9052D) / Modbus RTU (EX9052D-M)
Firmware Commands (ASCII Mode):
- `$AA6` – Read digital input status
- `$AALS` – Read latched input status
- `$AAC` – Clear latched inputs
- `$AAF` – Read firmware version
- `$AAM` – Read module name
- `%AANNTTCCFF` – Set address, type, baud rate, and format
- `~AA3EVV` – Set host watchdog timeout value
Safety & Reliability Features:
- Optical isolation prevents damage from voltage surges.
- EEPROM retains configuration during power loss.
- Watchdog timers prevent system lockup.
- LED indicators simplify diagnostics.
### Summary
The ExpertDAQ EX9052D is a robust, isolated 8-channel digital input module optimized for industrial automation and remote monitoring applications. Its combination of high isolation, flexible voltage compatibility, and reliable RS-485 communication makes it ideal for distributed control systems. The module’s dual watchdog design, EEPROM configuration retention, and extended temperature tolerance ensure dependable operation in demanding environments.
For Modbus-based systems, the EX9052D-M variant provides full Modbus RTU compliance, enabling seamless integration with standard industrial controllers and SCADA platforms. Both models exemplify ExpertDAQ’s focus on reliability, modularity, and ease of integration in industrial data acquisition networks.
### 1. Product Overview
Product Name: ExpertDAQ EX9052D
Model: EX9052D
Series: EX9000 Series – RS-485 Digital I/O Modules
Article Number: EX9052D
Manufacturer: ExpertDAQ (Expert Data Acquisition Systems)
The ExpertDAQ EX9052D is an industrial-grade digital input module designed for distributed data acquisition and control applications over an RS-485 network. It provides eight optically isolated digital input channels, combining six differential and two single-ended inputs, and is engineered for robust performance in harsh environments. The EX9052D is part of the ExpertDAQ EX9000 modular I/O family, which supports ASCII command communication, while its variant, the EX9052D-M, supports Modbus RTU protocol for seamless integration with PLCs, SCADA systems, and industrial automation controllers.
### 2. Key Features
- 8 Isolated Digital Inputs:
Six differential and two single-ended channels with common ground, providing flexible signal interfacing for various sensor types and logic levels.
- High Isolation Protection:
3750 Vrms optical isolation between channels and system logic ensures reliable operation and protection against ground loops and electrical noise.
- Wide Input Voltage Range:
Accepts digital logic levels from +4 VDC to +30 VDC for logic high (ON) and below +1 VDC for logic low (OFF), compatible with TTL, CMOS, and open-collector signal sources.
- RS-485 Communication Interface:
Two-wire half-duplex RS-485 interface supporting up to 256 modules on a single network segment (without repeater) and cable lengths up to 1200 meters.
- Flexible Communication Protocols:
- EX9052D: ASCII command set for direct serial control.
- EX9052D-M: Modbus RTU protocol for standardized industrial communication.
- LED Channel Indicators:
Eight front-panel LEDs provide real-time visual feedback of input channel status.
- Low Power Consumption:
Typical power consumption of 1.2 W at 10–30 VDC supply voltage.
- Extended Temperature Range:
Operates reliably from -25°C to +75°C, suitable for industrial and outdoor environments.
- Dual Watchdog System:
Hardware and software watchdogs ensure continuous operation and automatic recovery from communication or system faults.
- EEPROM Configuration Storage:
Retains module address, baud rate, and configuration settings even after power loss.
- Compact and Rugged Design:
Built for DIN-rail or panel mounting, with robust housing suitable for industrial control cabinets.
### 3. Technical Specifications
| Parameter | Specification |
|----------------|-------------------|
| Model | EX9052D |
| Input Channels | 8 total (6 differential, 2 single-ended with common ground) |
| Input Type | Optically isolated digital inputs |
| Input Voltage (ON) | +4 VDC to +30 VDC |
| Input Voltage (OFF) | +1 VDC maximum |
| Input Impedance | 3 kΩ |
| Isolation Voltage | 3750 Vrms channel-to-system |
| Interface | RS-485, 2-wire half-duplex |
| Communication Speeds | 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps |
| Protocol | ASCII (EX9052D), Modbus RTU (EX9052D-M) |
| Power Supply | +10 VDC to +30 VDC |
| Power Consumption | 1.2 W typical |
| LED Indicators | 8 input status LEDs |
| Operating Temperature | -25°C to +75°C |
| Storage Temperature | -30°C to +75°C |
| Isolation Type | Optical isolation per channel |
| Configuration Memory | EEPROM (non-volatile) |
| Mounting | DIN-rail or panel mount |
| Network Capacity | Up to 256 modules per RS-485 segment |
| Maximum Cable Length | 1200 m (without repeater) |
| Housing | Industrial-grade enclosure (material not specified) |
### 4. Functionality
The EX9052D functions as a distributed digital input acquisition module within an RS-485 network. It converts discrete input signals from sensors, switches, or logic devices into serial data for transmission to a host controller or SCADA system.
Operating Principle:
- Each input channel detects a digital signal (ON/OFF) based on voltage thresholds.
- The module optically isolates each input to prevent ground potential differences and electrical interference.
- Input states are continuously monitored and can be read via ASCII commands (EX9052D) or Modbus RTU registers (EX9052D-M).
- The module supports latched input detection, allowing capture of transient pulses that might otherwise be missed during polling.
Use Cases and Applications:
- Industrial automation and process control
- Remote monitoring of digital sensors and switches
- Machine status and alarm signal acquisition
- Building automation and energy management systems
- Distributed I/O expansion for PLCs and embedded controllers
Compatibility:
- Compatible with any RS-485 master device or Modbus RTU controller.
- Works with ExpertDAQ configuration utilities and third-party SCADA software.
- Supports integration with Modbus-compatible PLCs, HMIs, and data loggers.
### 5. Components & Accessories
Included Components:
- EX9052D module unit
- Terminal block connectors for signal and power wiring
- User manual and configuration guide
- Software utility for configuration (via RS-485)
Optional Accessories:
- RS-485 to USB or RS-232 converters for PC connection
- RS-485 repeaters for extended network distances
- DIN-rail mounting clips and brackets
- Power supply units (10–30 VDC regulated)
- Shielded twisted-pair communication cables
Connectors:
- Screw-type terminal blocks for input channels and power supply
- RS-485 communication terminals (Data+, Data–, GND)
- INIT* terminal or rear-mounted switch for configuration reset
### 6. Installation & Setup
Requirements:
- DC power supply between 10 and 30 VDC
- RS-485 network connection (2-wire)
- Host controller or PC with RS-485 interface
Mounting Options:
- DIN-rail mounting in control cabinets
- Panel mounting using screws or brackets
Configuration Procedure:
1. Power Connection: Connect +V and GND to a regulated DC power source.
2. RS-485 Wiring: Connect Data+ and Data– lines to the network bus.
3. Address and Baud Rate Setup:
- Default address: 01
- Default baud rate: 9600 bps
- Configuration via ASCII command `%AANNTTCCFF` or software utility.
4. INIT* Mode:
- Activate by connecting INIT* to GND or sliding the INIT* switch to ON.
- Used for resetting configuration or changing baud rate/checksum.
5. Verification:
- Use command `$AA6` or Modbus function code 0x01 to read input status.
- Verify LED indicators correspond to input signal states.
Wiring Examples:
- Dry Contact Input: Connect switch contacts directly between input and ground.
- TTL/CMOS Input: Connect logic output to input terminal with shared ground.
- Open Collector Input: Connect transistor output to input terminal with pull-up voltage.
### 7. Performance & Capabilities
- Speed and Responsiveness:
Supports baud rates up to 115.2 kbps, allowing fast polling and data acquisition across large networks.
- Capacity:
Each module provides 8 input channels; up to 256 modules can be networked, yielding a total of 2048 digital inputs per RS-485 segment.
- Efficiency:
Low power consumption (1.2 W) minimizes heat generation and allows dense installation.
- Reliability:
Dual watchdog system ensures continuous operation:
- Module Watchdog: Hardware circuit monitors internal operation and resets the module if a fault occurs.
- Host Watchdog: Software timer monitors communication from the host; if timeout occurs, the module enters a safe state.
- Limitations:
- No digital output capability (input-only module).
- ASCII version (EX9052D) does not support Modbus RTU.
- Requires external RS-485 converter for PC connection.
### 8. Standards & Compliance
- Communication Standards:
RS-485 (EIA/TIA-485) compliant, supporting multi-drop serial communication.
- Protocol Standards:
- ASCII command set (ExpertDAQ proprietary)
- Modbus RTU (for EX9052D-M variant)
- Electrical Isolation:
3750 Vrms optical isolation per channel, meeting industrial safety and EMC requirements.
- Environmental Compliance:
Designed for industrial temperature range (-25°C to +75°C) and high electrical noise immunity.
- Regulatory Compliance:
Conforms to CE and FCC Class A industrial emissions standards (typical for ExpertDAQ modules).
### 9. Additional Information
Warranty:
Standard manufacturer warranty (typically 2 years, depending on region and distributor).
Technical Support:
ExpertDAQ provides technical documentation, configuration utilities, and firmware updates via its official website. Support includes:
- Configuration assistance
- Firmware upgrade instructions
- RS-485 network troubleshooting guides
Maintenance:
- Periodic inspection of wiring and terminal connections recommended.
- Ensure proper grounding and shielding for noise immunity.
- Firmware updates can be applied via RS-485 interface when available.
Firmware & Updates:
- Firmware version can be read using command `$AAF`.
- Example: `$01F` → `!01D04.03` indicates firmware version D04.03.
- Updates may include enhanced Modbus mapping or improved watchdog handling.
Modbus Mapping (EX9052D-M):
| Address Range | Function | Access | Description |
|--------------------|--------------|-------------|-----------------|
| 00033–00040 | Digital Input Channels DI0–DI7 | Read | Current input states |
| 00065–00072 | DI Latch High | Read | Indicates channels that have latched high |
| 00097–00104 | DI Latch Low | Read | Indicates channels that have latched low |
| 00264 | Clear Latch | Write | Clears latched input states |
| 30001–30008 | DI Counters | Read | 16-bit input pulse counters |
| 00513–00520 | Clear DI Counters | Write | Resets input counters |
Default Communication Settings:
- Address: 01
- Baud Rate: 9600 bps
- Data Format: 8N1 (8 data bits, no parity, 1 stop bit)
- Protocol: ASCII (EX9052D) / Modbus RTU (EX9052D-M)
Firmware Commands (ASCII Mode):
- `$AA6` – Read digital input status
- `$AALS` – Read latched input status
- `$AAC` – Clear latched inputs
- `$AAF` – Read firmware version
- `$AAM` – Read module name
- `%AANNTTCCFF` – Set address, type, baud rate, and format
- `~AA3EVV` – Set host watchdog timeout value
Safety & Reliability Features:
- Optical isolation prevents damage from voltage surges.
- EEPROM retains configuration during power loss.
- Watchdog timers prevent system lockup.
- LED indicators simplify diagnostics.
### Summary
The ExpertDAQ EX9052D is a robust, isolated 8-channel digital input module optimized for industrial automation and remote monitoring applications. Its combination of high isolation, flexible voltage compatibility, and reliable RS-485 communication makes it ideal for distributed control systems. The module’s dual watchdog design, EEPROM configuration retention, and extended temperature tolerance ensure dependable operation in demanding environments.
For Modbus-based systems, the EX9052D-M variant provides full Modbus RTU compliance, enabling seamless integration with standard industrial controllers and SCADA platforms. Both models exemplify ExpertDAQ’s focus on reliability, modularity, and ease of integration in industrial data acquisition networks.
No accessories available.