LOOKING FOR THE RIGHT

INDUSTRIAL SOLUTION?

Discover embedded, communication and automation solutions tailored to your application.

NDS-OPC

OPC driver for NuDAM moduls
  • Manufacturer Adlink Technology Inc.
  • Category: RS485 DIN Rail IO Modules
  • The NDS‑OPC is an OPC (OLE for Process Control) server software package developed by ADLINK Technology Inc. for use with NuDAM data acquisition and control modules. It provides a standardized communication interface between NuDAM hardware and any OPC‑compliant client application, enabling seamless data monitoring, control, and integration within Windows‑based industrial automation systems.
- Full‑Function OPC Server: Implements the complete OPC Data Access interface, allowing real‑time data exchange between NuDAM modules and OPC clients.
- Wide Compatibility: Works with any OPC‑compliant client software, including SCADA, HMI, and custom industrial control applications.
- Integrated Configuration Utility (NuDAM Explorer): A graphical tool for configuring both hardware and server parameters, simplifying setup and reducing configuration time.
- Interactive Module Configuration: Enables users to set module parameters such as input range, data format, and filtering directly through the Explorer interface.
- Customizable Server Operation: Users can define I/O scan times, timeout limits, and assign descriptive names (tags) to each data item for easy identification in client applications.
- Sample OPC Client Application: Includes a fully functional sample client (OpcClient.exe) demonstrating digital input/output (DI/DO) and analog input/output (AI/AO) operations.
- Flexible Installation Options: Offers Typical, Compact, and Custom installation modes to suit different deployment needs.
- DCOM‑Based Communication: Utilizes Microsoft’s Distributed Component Object Model (DCOM) for local and remote OPC communications.
- Comprehensive Documentation: Includes user guides, installation manuals, and reference documentation in both help and PDF formats.
- Automatic System Registration: The installation process registers the OPC server (NDOPCSvr.EXE) within the Windows system registry for immediate use.

Country of origin: Taiwan R.O.C.

Comprehensive Product Summary – NDS‑OPC (OPC Driver for NuDAM Modules)




### 1. Product Overview

Product Name: NDS‑OPC
Model: NDS‑OPC
Series: NuDAM Software Integration Tools
Article Number: NDS‑OPC
Manufacturer: ADLINK Technology Inc.
Manual Revision: Rev. 1.00b (September 6, 1999)
Copyright: © 1998–1999 ADLINK Technology Inc. All rights reserved.

Product Description:
The NDS‑OPC is an OPC (OLE for Process Control) server software package developed by ADLINK Technology Inc. for use with NuDAM data acquisition and control modules. It provides a standardized communication interface between NuDAM hardware and any OPC‑compliant client application, enabling seamless data monitoring, control, and integration within Windows‑based industrial automation systems.

Supported Operating Systems:
- Microsoft Windows 95 (with DCOM for Windows 95 installed)
- Microsoft Windows 98
- Microsoft Windows NT 4.0 or higher




### 2. Key Features

- Full‑Function OPC Server: Implements the complete OPC Data Access interface, allowing real‑time data exchange between NuDAM modules and OPC clients.
- Wide Compatibility: Works with any OPC‑compliant client software, including SCADA, HMI, and custom industrial control applications.
- Integrated Configuration Utility (NuDAM Explorer): A graphical tool for configuring both hardware and server parameters, simplifying setup and reducing configuration time.
- Interactive Module Configuration: Enables users to set module parameters such as input range, data format, and filtering directly through the Explorer interface.
- Customizable Server Operation: Users can define I/O scan times, timeout limits, and assign descriptive names (tags) to each data item for easy identification in client applications.
- Sample OPC Client Application: Includes a fully functional sample client (OpcClient.exe) demonstrating digital input/output (DI/DO) and analog input/output (AI/AO) operations.
- Flexible Installation Options: Offers Typical, Compact, and Custom installation modes to suit different deployment needs.
- DCOM‑Based Communication: Utilizes Microsoft’s Distributed Component Object Model (DCOM) for local and remote OPC communications.
- Comprehensive Documentation: Includes user guides, installation manuals, and reference documentation in both help and PDF formats.
- Automatic System Registration: The installation process registers the OPC server (NDOPCSvr.EXE) within the Windows system registry for immediate use.




### 3. Technical Specifications

Software Type: OPC Server Software Package
Supported Hardware: ADLINK NuDAM series data acquisition and control modules (e.g., ND‑6060, ND‑6012, ND‑6021)
Supported Operating Systems: Windows 95/98/NT 4.0 or later
System Requirements:
- IBM PC/AT or compatible computer
- Windows NT 4.0 (Service Pack 2 or higher recommended) or Windows 95/98 with DCOM enabled
- Hard disk with sufficient space for installation (typical installation < 50 MB)
- CD‑ROM drive for installation media
- Available COM port for NuDAM module connection (e.g., COM1)

File Components (Typical Installation):
- NuDAMExplorer.EXE: Graphical configuration utility
- NDOPCSvr.EXE: Core OPC server executable
- NuDAMDrv.DLL: NuDAM driver library
- Server.cfg: Server configuration file (contains scan speed and configuration data)
- Demo.adl: Example configuration file defining sample modules (ND6060, ND6012, ND6021)
- Explorer.HLP / Explorer.CNT: Help files for NuDAM Explorer
- OPCInterface.HLP / OPCInterface.CNT: Help files for OPC interface reference
- Doc Directory: Contains PDF documentation (NuDAMOPC.PDF, NDOPCInstall.PDF)
- Samples Directory: Contains sample OPC client program (OpcClient.EXE) and source code (VC++ 5.0 project)

System DLLs Installed:
- VCL35.VPL
- OPCProxy.DLL

Registry Entries:
- NDOPCSvr.EXE registered as a COM server component




### 4. Functionality

Operational Overview:
NDS‑OPC acts as a middleware layer between NuDAM hardware modules and OPC client applications. It translates NuDAM communication protocols into standardized OPC data objects accessible through the OPC Data Access interface.

Core Components:
1. OPC Server (NDOPCSvr.EXE): Manages communication with NuDAM modules, handles data acquisition, and exposes data items to clients.
2. NuDAM Explorer: Provides a user interface for configuring both hardware and server parameters.
3. Configuration Files: Store system setup, including module addresses, scan intervals, and tag definitions.

Use Cases and Applications:
- Industrial process monitoring and control
- Data acquisition systems
- SCADA and HMI integration
- Laboratory automation
- Remote I/O management via serial communication

Compatibility:
- Compatible with any OPC Data Access (DA) compliant client software.
- Supports integration with Microsoft Visual C++‑based applications and other OPC‑enabled environments.




### 5. Components & Accessories

Included Software Components:
- NDS‑OPC installation package (on ADLINK All‑in‑One CD)
- NuDAM Explorer configuration utility
- NuDAM OPC Server executable
- NuDAM driver DLL
- Sample OPC client application (OpcClient.exe)
- Documentation and help files

Optional Add‑Ons:
- Additional NuDAM hardware modules (ND‑series)
- Visual C++ 5.0 development environment (for sample source compilation)
- DCOM for Windows 95 (if applicable)

Connectors and Interfaces:
- Serial communication via COM port (RS‑232/RS‑485 depending on NuDAM module)
- Software interface via OPC COM/DCOM protocol




### 6. Installation & Setup

System Requirements Recap:
- Windows 95/98/NT 4.0 with DCOM enabled
- CD‑ROM drive
- Sufficient disk space
- NuDAM modules connected to a serial port

Installation Procedure:
1. Insert the ADLINK All‑in‑One CD into the CD‑ROM drive.
2. If autorun does not start, manually execute `x:\setup` (where *x* is the CD‑ROM drive letter).
3. Select Software Package → NDS‑OPC from the installation menu.
4. Enter user information and a valid serial number. Without a valid license, the software runs in a 120‑minute demo mode.
5. Choose installation directory (default: `C:\Program Files\ADLINK\NuDAMOPC`).
6. Select installation type:
- Typical: Installs all components (recommended).
- Compact: Installs essential components only.
- Custom: Allows manual selection of components.
7. Complete installation and click Finish.

Post‑Installation Configuration:
- Verify that NDOPCSvr.EXE is registered in the system registry.
- Confirm that DCOM settings are enabled in Windows registry:
```
HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\OLE\EnableRemoteConnect = 'Y'
HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\OLE\EnableDCOM = 'Y'
```
- For Windows 95, install “DCOM for Windows 95” from Microsoft or Visual C++ 5.0 CD.

Sample Program Setup:
1. Connect NuDAM modules (ND6060, ND6012, ND6021) to COM1 with addresses 6, 2, and 11 respectively.
2. Launch NuDAMExplorer.EXE and open Demo.adl configuration file.
3. Save configuration as Server.cfg.
4. Exit Explorer and start OpcClient.EXE.
5. Click Connect to launch the OPC server and establish communication.
6. Monitor or control module I/O using the client interface.




### 7. Performance & Capabilities

Data Communication:
- Real‑time data acquisition and control through OPC Data Access interface.
- Supports synchronous and asynchronous read/write operations.

OPC Interface Implementation:
Implements standard OPC interfaces including:
- IOPCServer: Group management, error handling, and status retrieval.
- IOPCGroupStateMgt: Group state management and cloning.
- IOPCSyncIO / IOPCAsyncIO: Synchronous and asynchronous I/O operations.
- IOPCItemMgt: Item management (add, validate, remove, activate, datatype assignment).
- IDataObject: Data advisory connections for event notifications.

Performance Parameters:
- Configurable I/O scan time and timeout limits.
- Supports multiple groups and items per server instance.
- Efficient communication with multiple NuDAM modules over serial link.

Limitations:
- Designed for Windows 95/98/NT environments only (no native support for modern Windows versions).
- Requires manual DCOM configuration for remote access under Windows 95.
- Demo mode limited to 120 minutes without valid license key.




### 8. Standards & Compliance

Industry Standards:
- OPC Data Access (DA) Specification: Fully compliant with OPC Foundation standards for data access.
- Microsoft COM/DCOM Architecture: Utilizes standard COM interfaces for inter‑process communication.

Regulatory and Software Compliance:
- Compatible with Microsoft Windows operating systems (95/98/NT).
- Requires DCOM configuration in accordance with Microsoft guidelines.

Trademarks and Intellectual Property:
- NuDAM and NDS‑OPC are registered trademarks of ADLINK Technology Inc.
- IBM PC is a registered trademark of International Business Machines Corporation.
- Intel is a registered trademark of Intel Corporation.
- Other product names are trademarks or registered trademarks of their respective owners.




### 9. Additional Information

Warranty and Liability:
ADLINK Technology Inc. provides this software “as is” without warranty of any kind. The company assumes no liability for direct, indirect, incidental, or consequential damages arising from the use or inability to use the product or documentation.

Support and Service:
ADLINK emphasizes customer satisfaction and provides multiple support channels:
- Website: [http://www.adlink.com.tw](http://www.adlink.com.tw)
- General Service: service@adlink.com.tw
- Product‑Specific Contacts:
- NuIPC: nuipc@adlink.com.tw
- NuDAQ: nudaq@adlink.com.tw
- NuDAM: nudam@adlink.com.tw
- NuPRO: nupro@adlink.com.tw
- Software: sw@adlink.com.tw
- AMB: amb@adlink.com.tw
- Fax: +886‑2‑2249‑3235 (Attn: ADLINK Service)

When requesting support, users should provide:
- Contact information (name, company, phone, fax, email)
- Product model and purchase date
- Operating environment (OS, hardware configuration, BIOS, network card, etc.)
- Detailed problem description

Maintenance and Updates:
- Users are encouraged to check ADLINK’s website for updated drivers, documentation, and service packs.
- Configuration files and registry entries should be backed up before performing updates.

Documentation Included:
- *NuDAM OPC Server User’s Guide*
- *NuDAM OPC Server Reference Manual (PDF)*
- *Installation Guide (NDOPCInstall.PDF)*
- Online help files for Explorer and OPC Interface

Version Control:
- Manual Revision: 1.00b
- Release Date: September 6, 1999




### Summary

The ADLINK NDS‑OPC software package is a robust, standards‑compliant OPC server designed to integrate NuDAM data acquisition modules into Windows‑based automation systems. It provides a complete OPC Data Access interface, enabling seamless communication between hardware and client applications. With its intuitive NuDAM Explorer configuration tool, flexible installation options, and comprehensive documentation, NDS‑OPC simplifies the deployment of distributed data acquisition and control systems.

By adhering to OPC and DCOM standards, NDS‑OPC ensures interoperability with a wide range of industrial software platforms, making it a reliable choice for engineers and system integrators seeking to unify data communication across diverse automation environments.

No accessories available.